Installation and operating manual
KT-Elektronik
CO6: Modbus
F
Function
FS
Sys.
Function block parameter description/value range
(factory default setting)
01 Modbus
1
all
CO6 -> F01 - 1: Modbus active
02 Modbus-16-bit
addressing
0
all
only with CO6 -> F01 – 1
CO6 -> F02 - 1: 16-bit addressing,
CO6 -> F02 - 0: 8-bit addressing
03 Modem function
0
all
CO6 -> F03 - 1 only with • CO6 -> F01 - 1
• CO6 -> F08 - 1
04 Automatic Modem
configuration
0
all
CO6 -> F04 - 1 only with • CO6 -> F03 - 1
• CO6 -> F08 - 1
05 Blocking the
BCS dial up
0
all
CO6 -> F05 - 1: no dial up on failure,
only with CO6 -> F03 - 1
06 BCS dial up
on corrected
failures
0
all
CO6 -> F06 - 1: additional dial up on corrected
failures, only with CO6 -> F03 - 1
07 Control system
monitoring
all
CO6 -> F07 - 1: Reset all collective level bits to
"autonomous" on missing connection,
only with CO6 -> F01 – 1
08 SMS
CO6 -> F08 - 1: SMS delivery active
F Function block number, FS factory setting, Sys System variant ID
10.2 Parameter lists
PA3: Solar circuit parameter level
Symbol/Icon
Parameter name
Value range (factory default)
ST O P
s
Minimum running time after which the
collector pump is earliest stopped
0...1800 s (60 s)
STA RT
s
Minimum idle time after which the collector
pump is earliest started
0...1800 s (180 s)