7.9 Data Logging
The data logging module (part no. 1400-9378) allows saving the following controller data
in two minute intervals:
Sensor readings
Switching states of the pump outlets
Error status register and archive
Access to controller settings
The connector for the data logging module
is located on the left side (front panel view)
inside the controller housing (RJ45 connector)
.
Once the memory chip of the data logging module is full, approx. after 8 days, the
module starts overwriting the oldest data. The current memory capacity can be viewed in
the advanced information level, it is the second value displayed (range: 0 to 6035) in
menu item "Info 2". After plugging in the data logging module, the value is not displayed
before the first scanning cycle is complete.
The saving cycle interval in minutes, range from 1 to 99 minutes, can be programmed
after entering the access code 0010. The default factory setting of 2 corresponds to a
two minute cycle interval.
The data can be analysed using the PC based software "Data Logging Viewer". The
USB converter 3 (part no. 1400-9377) which is shipped with the viewer software is
required to connect the logging module to a PC.
A device description file is also required to display the data correctly.