Battery abnormal BCB trip:
Enable or disable BCB trip single output. The default value
is Disable.
Bypass Feedback:
Enable or disable bypass feedback output. The default value is
Disable.
External Maint. breaker:
Enable or disable external maintenance breaker connection
detection. The default value is Disable.
Battery Switch:
Enable or disable battery breaker connection detection. The default
value is Disable.
Output Switch:
Enable or disable output breaker connection detection. The default
value is Disable.
Bypass Switch:
Enable or disable bypass breaker connection detection. The default
value is Disable.
Battery ground Fault:
Enable or disable battery grounding failure detection. The default
value is Disable.