52
Freq Conv Mode:
Frequency conversion mode, enable: output frequency set 50Hz or
60Hz, input frequency is 60Hz or 50Hz, UPS no alarm not battery
and bypass abnormal. Default is Disable.
LBS mode:
setting value: LBS disable, LBS master, LBS slave. Default is LBS disable.
Temp Sensor Switch:
temperature sensor compensation switch, when need to connect
battery temperature sensor, please charge the value to enable.
Temp Sensor Select:
temperature sensor type select. Has tow types: NTC and RS485.
NTC for single and short distance. Rs485 for multiple and far
distance.
Power Walk in:
this is enable the UPS to control the interval that each module transfers
from battery mode to normal mode, which reduces the impact on the
generator or power grid. The value can be 1~20, default value is 1.
Inter Power Walk in:
this is enable the UPS to control the interval that each rack
transfers from battery mode to normal mode, which reduces the impact on
the generator or power grid. The value can be 0~200, default value is 10.
Содержание HPM3300E
Страница 6: ...5 Front View Rear View 60kVA 80kVA 100kVA N 1 with Maintenance breaker Front View Rear View ...
Страница 9: ...8 3 2 2 Sub Rack UPS 60kVA 80kVA 100kVA N 1 without breaker Front View Rear View ...
Страница 17: ...16 3 4 1 2 Remove the screws M4 18PCS of the front side and rear side to remove the right and left covers ...
Страница 38: ...37 clicking on the block 4 3 2 Status View the voltage and current of the main bypass output battery can also ...
Страница 43: ...42 ...
Страница 48: ...47 ...
Страница 61: ...60 4 3 5 Maint Software update Touch correction history download and battery self test ...
Страница 62: ...61 4 3 5 1 USB Wizard History Output download history and setting record by USB 4 3 5 1 1 Alarm Log Output ...