background image

Caution

Caution

Caution

Caution

RPH

10

5.4

Connecting the piping

Never use the pump itself as an anchorage

point for the piping. The permissible pipeline

forces must not be exceeded (see section 4.3.5).

Suction lift lines shall be laid with a rising slope towards the

pump and suction head lines with a downward slope towards

the pump. The pipelines shall be anchored in close proximity to

the pump and connected without transmitting any stresses or

strains. The nominal diameters of the pipelines shall be at least

equal to the nominal diameters of the pump nozzles. The

mating flanges must be parallel to the pump flanges.

It is recommended to install check and shut-off elements in the

system, depending on the type of plant and pump. It must be

ensured, however, that the pump can still be drained and

dismantled without problems.
Thermal expansions of the pipelines must be compensated by

appropriate measures so as not to impose any extra loads on

the pump exceeding the permissible pipeline forces and

moments.

An excessive, impermissible increase in the pipeline

forces may cause leaks on the pump where the fluid

handled can escape into the atmosphere.

Danger to life when toxic or hot fluids are handled!

The flange covers on the pump suction and discharge nozzles

must be removed prior to installation in the piping.

Please check if a strainer/filter should be fitted

in the suction line during the commissioning

stage, in order to protect both the pump and the shaft seal from

damage due to contamination from the plant.

In order to avoid any marked deterioration of the

NPSHavailable, which would have an adverse effect on the

pump, the strainer has to be cleaned whenever required. It is

recommended to use a differential pressure gauge to detect

any strainer clogging (see 6.1.6).

For installation on a foundation with vibration insulation

please take into account when connecting the piping

that the flexible elements at the baseplate may only

compensate compressive and shearing strains within the

admissible limits. Tensile strains cannot be compensated for,

therefore the flexible elements shall only be firmly fastened to

the foundation after the piping has been connected.

5.4.1

Auxiliary connections

The dimensions and locations of the auxiliary connections

(cooling, heating, barrier liquid, flushing liquid, etc.) are

indicated on the general arrangement plan or piping layout.

These connections are required for proper

functioning of the pump and are therefore of

vital importance!

Modifications are only permitted after prior consultation with the

manufacturer (see 2.7)!

5.4.2

Coupling guard

In compliance with the accident prevention regulations

the pump must not be operated without a coupling

guard. If the customer specifically requests not to include a

coupling guard in our delivery, then the operator must supply

one. In this case, it is important to make sure that the materials

selected for coupling and coupling guard are non-sparking in

the event of mechanical contact. KSB’s scope of supply meets

this requirement.

5.5

Final check

Re-check the alignment as described in section 5.3 and verify

the correct distance between the coupling and the coupling

guard.

It must be easy to rotate the shaft by hand at the coupling.

5.6

Connection to power supply

Connection to the power supply must be effected by a

trained electrician only. Check available mains voltage

against the data on the motor rating plate and select appropriate

start-up method.

We strongly recommend to use a motor protection device

(motor protection switch).

In potentially explosive atmospheres, compliance with

IEC60079-14 is an additional requirement for electrical

connection.

6

Commissioning, start-up / shutdown

Compliance with the following requirements is

of paramount importance. Damage resulting

from non-compliance shall not be covered by the scope of

warranty.

6.1

Commissioning

Before starting up the pump make sure that the following

requirements have been checked and fulfilled.
If a constant-level oiler is provided, screw same into the tapping

hole provided in the bearing bracket prior to adding the oil (see

6.1.1).

On cooled bearing brackets, fitting the constant-level oiler is

difficult due to the position of the cooling line. The connection

elbow of the constant-level oiler must be screwed in separately,

after having removed the protective cage and oil reservoir.

Afterwards, screw the oil reservoir back on and cover with the

protective cage.

The connection between bearing bracket and constant-level

oiler shall be sealed with PTFE tape, if necessary.
The operating data, the oil level, if applicable (6.1.1), and the

direction of rotation (6.1.4) must have been checked. The pump

must have been primed (6.1.3).

Also verify the following:
-

Make sure that the unit has been properly connected to the

electric power supply and is equipped with all protection

devices.

-

Make sure that all auxiliary lines (5.4.1) are connected and

functioning.

-

If the pump has been out of service for a longer period of

time, proceed in accordance with section 6.4.

On pumps delivered without a baseplate, the leakage line (part

No. 710.22) must be added as well.

6.1.1

Lubricants
Oil lubricated bearings

The bearing bracket has to be filled with lubricating oil. The oil

quality required is outlined in section 7.2.2.3 and the quantity in

section 7.2.2.4.

Oil level in reservoir

during filling procedure

Vent / Filler

plug

Oil level

sight glass

Position of reservoir for topping

up oil

Oil level in bearing bracket

and connection elbow

Fig. 9

Oil fill

Procedure:

Remove the protective cage of the constant-level oiler.

Unscrew vent plug. Pour in the oil through the vent plug tapping

hole after having hinged down the reservoir of the

constant-level oiler until oil appears in the vertical portion of the

connection elbow (Fig. 9).

Содержание RPH Series

Страница 1: ...______________________ Type series __________________________________ These operating instructions contain fundamental information and precautionary notes Please read the manual thoroughly prior to installation of unit connection to the power supply and commissioning It is imperative to comply with all other operating instructions referring to components of this unit This manual shall always be ke...

Страница 2: ...rd 10 5 5 Final check 10 5 6 Connection to power supply 10 Page 6 Commissioning start up shutdown 10 6 1 Commissioning 10 6 1 1 Lubricants 10 6 1 2 Shaft seal 11 6 1 3 Priming the pump and checks to be carried out 11 6 1 4 Checking the direction of rotation 11 6 1 5 Cleaning the plant piping 11 6 1 6 Start up strainer 11 6 1 7 Start up 12 6 1 8 Shutdown 12 6 2 Operating limits 12 6 2 1 Temperature...

Страница 3: ...ooled uncoooled 9 1 21 Measures to be taken for prolonged shutdown 6 3 2 13 Mechanical seal installation 7 5 4 16 Minimum Maximum Flow 6 2 5 12 Section Page Noise characteristics 4 3 6 8 Non compliance with safety instructions 2 3 4 Operating limits 6 2 12 Permissible forces and moments at the pump nozzles 4 3 5 7 Personnel qualification and training 2 2 4 Place of installation 5 3 2 9 Priming the...

Страница 4: ...indicating the direction of rotation markings for fluid connections must always be complied with and be kept in a perfectly legible condition at all times 2 2 Personnel qualification and training All personnel involved in the operation maintenance inspection and installation of the unit must be fully qualified to carry out the work involved Personnel responsibilities competence and supervision mus...

Страница 5: ...s during the installation phase the direction of rotation must never be checked by starting up the unfilled pump unit even for a short period to prevent temperature increases resulting from contact between rotating and stationary components 2 9 4 Pump operating mode Make sure that the pump is always started up with the suction side shut off valve fully open and the discharge side shut off valve sl...

Страница 6: ...the pump unit slips out of the suspension arrangement it may cause personal injury and damage to property D00311 Fig 1 Transport of the pump Fig 2 Transport of the complete unit 3 2 Interim storage indoors Preservation When the unit is temporarily put into storage only the wetted low alloy components e g JL 1040 JS 1030 A 216 Gr WCB etc must be preserved Commercially available preservatives can be...

Страница 7: ...chanical seal drawing 4 3 4 Bearings 4 3 4 1 Design specifications The shaft is supported byoil lubricatedrolling elementbearings The motor end bearing is a fixed bearing whose axial bearing clearance limits the axial movement of the rotor The standard motor end bearing is a paired angular contact ball bearing For high inlet pressures a triple bearing assembly is used see section 9 design variants...

Страница 8: ...65 5 63 5 76 0 70 0 67 5 22 0 68 0 66 5 64 5 76 5 70 5 68 0 30 0 70 0 68 0 66 0 78 0 72 0 69 5 37 0 71 0 69 5 67 0 78 5 72 5 70 0 45 0 72 0 70 5 68 0 79 5 73 5 71 0 55 0 73 0 71 5 69 0 80 0 74 0 71 5 75 0 74 5 73 0 70 5 81 0 75 5 72 5 90 0 75 5 74 0 71 0 81 5 76 0 73 0 110 0 77 0 75 0 72 0 82 0 76 5 74 0 132 0 78 0 76 0 73 0 82 5 77 0 74 5 160 0 79 0 77 0 74 0 83 5 78 0 75 0 200 0 80 0 78 0 75 0 8...

Страница 9: ...om each shaft at all points around the circumference In addition the distance between the two coupling halves must remain the same all around the circumference Use a feeler gauge a wedge gauge or a dial micrometer to verify see Fig 6 and Fig 7 Straight edge Straight edge Gauge a a b b Fig 6 Aligning the coupling with the help of a gauge and a straight edge a b a b Gauge Straight edge Straight edge...

Страница 10: ...delivery then the operator must supply one In this case it is important to make sure that the materials selected for coupling and coupling guard are non sparking in the event of mechanical contact KSB s scope of supply meets this requirement 5 5 Final check Re check the alignment as described in section 5 3 and verify the correct distance between the coupling and the coupling guard It must be easy...

Страница 11: ...6 Bearing bracket 200 1 250 bis 315 2 0 2 Bearing bracket 315 3 0 2 Support on baseplate 250 0 2 1 For n 35001 min andn 2900 1 minin conjunctionwith triplebearing assembly In all other cases from 250 C 2 Water cooling or fan impeller 3 Water cooling and optional fan impeller The cooling liquid quantities indicated are based on Dt max 15 C 6 1 3 1 2 Cooling of heat exchanger For mechanical seals wi...

Страница 12: ...e 7 2 1 The safety instructions set forth in section 2 9 must be complied with 6 2 1 1 Heating the stand by pump To make sure that the stand by pump is operational at all times and to keep it warm no special precautions need to be taken provided all cooling points are in operation and the permissible nozzle forces and moments are not exceeded For extreme operating conditions please contact KSB Peg...

Страница 13: ...ghtly open for a short period of time the permissible pressure and temperature limits must not be exceeded A special design is required to comply with temperature class T6 in the bearing area In such cases and if am bient temperature exceeds 40 C contact the manufacturer Verify correct oil level as described in section 6 1 1 The shut off elements and the auxiliary feed lines must not be closed dur...

Страница 14: ...0 02 and remove seal cover 471 01 Cooled version Note position of O rings 412 01 31 Pull seal cartridge out of casing cover 161 Please observe the mechanical seal drawing Proceed in line with this drawing if further dismantling of the mechanical seal is required If required refer to the supplementary sheet 11 Undo the hex socket head cap screw in the coupling hub and use an extractor to pull the c...

Страница 15: ...ed nut slip on lockwasher tighten keywayed nut and bend over lockwasher 2 Cooled version Note position of O rings 412 01 31 3 For mounting the mechanical seal proceed as described on the supplementary sheet if necessary Observe the instructions in section 7 5 4 4 Check the sliding fit of the shaft protecting sleeve on the shaft if fitted 5 Carefully insert the impeller joint ring making sure the r...

Страница 16: ...0 B06 20 M 24 5653 4 4 M24 290 8 M 16 190 4 M20 270 1 M 30x1 5 400 6 5 200 670 06 24 565 9704 90 8 6 90 0 0 30 5 00 300 5 250 630 20 250 710 24 3 For material 1 7709 A 193 Grade B7 B16 4 For material 1 6772 Monix 3K A 540 Grade B24 5 For material 1 4571 A 276 Type 316Ti 6 For material 1 4021 A 276 Type 420 The values do not apply if general assembly drawings or other instructions state different v...

Страница 17: ...5 100 450 175 0 6 3 0 45 195 0 7 4 0 48 150 230 195 0 7 4 0 48 195 0 7 4 0 48 150 280 195 0 7 4 0 48 195 0 7 4 0 48 150 360 195 0 7 4 0 48 195 0 7 4 0 48 150 450 200 0 7 4 0 48 235 0 7 4 0 53 200 280 225 0 7 4 0 50 225 0 7 4 0 50 200 360 235 0 7 4 0 53 280 0 7 5 0 58 200 450 235 0 7 4 0 53 280 0 7 5 0 58 150 501 225 0 7 5 0 5 225 0 7 5 0 5 200 401 250 0 6 3 0 53 250 0 6 3 0 53 200 501 255 0 6 5 0 ...

Страница 18: ...02 322 01 330 433 502 01 02 1 503 01 02 1 542 02 Shaft Impeller Angular contact ball bearing set Cylindrical roller bearing Bearing bracket Mech seal Spring loaded ring Seat ring O rings Secondary seals at seat ring Spring set Casing wear ring Impeller wear ring Throttling bush Other sealing elements 1 1 1 1 2 2 2 2 1 2 2 1 4 1 1 1 1 3 3 3 3 1 2 2 1 6 1 1 2 2 4 4 4 4 1 2 2 2 8 2 2 2 2 5 5 5 5 1 3 ...

Страница 19: ...2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 4 5 2 2 3 4 2 2 3 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 5 5 5 5 6 6 6 6 7 7 7 9 5 5 7 9 6 6 6 7 7 7 7 9 5 5 5 5 6 6 6 6 7 7 7 9 5 5 7 9 6 6 6 7 7 7 7 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 B05S 80 450 100 360 100 450 ...

Страница 20: ...n of rotation Interchange two of the phases of the power supply cable Motor is running on two phases only Replace the defective fuse Check the electric cable connections Speed is too low 2 Increase speed Defective bearing s Fit new bearing s Insufficient rate of flow Increase the minimum rate of flow Wear of internal pump parts Replace worn components by new ones Pump back pressure is lower than s...

Страница 21: ...with impeller wear ring 503 01 02 grub screw 904 06 07 joint ring 411 31 32 67 optional lockwasher 931 02 320 02 550 2 Angular contact ball bearing with ring 550 adjusting washer 322 01 Cylindrical roller bearing 330 Bearing bracket compl with protective cage 169 10 bearing cover 360 01 02 gasket 400 01 O ring 412 22 constant level oiler 638 oil level sight glass 642 pipe 710 22 hex head bolt 901 ...

Страница 22: ...0 Impeller with impeller wear ring 503 01 02 grub screw 904 06 07 joint ring 411 31 32 optional 260 Impeller hub cap 320 02 Angular contact ball bearing 322 01 Cylindrical roller bearing 330 Bearing bracket compl with protective cage 169 10 bearing cover 360 01 02 gasket 400 01 O ring 412 22 constant level oiler 638 oil level sight glass 642 pipe 710 22 hex head bolt 901 31 37 vent plug 913 03 plu...

Страница 23: ...ring bracket cooled Tandem bearings Special pump designs for high inlet pressure Special pump design with thrower Pump design with plug 916 01 Part No Description 508 01 Oil thrower 904 20 Grub screw 916 01 Plug D01043 D01044 D01047 D01044 ...

Страница 24: ...able casing Oil mist lubrication D01126 D01127 KSB Aktiengesellschaft P O Box 1361 91253 Pegnitz Bahnhofplatz 1 91257 Pegnitz Germany Tel 49 9241 71 0 Fax 49 9241 71 1791 www ksb com RPH Performance curves For individual characteristic curves refer to offer curves 1316 451 and 1316 461 ...

Отзывы: