background image

moviBOOST VPt / CL

2

Work on the machine / unit must be carried out only during

standstill. The shutdown procedure described in the manual for

taking the unit out of service must be adhered to without fail.
Pumps or pump units handling fluids injurious to health must be

decontaminated.
Immediately following completion of the work, all safety-relevant

and protective devices must be re-installed and / or re-activated.

Please observe all instructions set out in the chapter on

“Commissioning / start-up” before returning the unit to service.

2.7

Unauthorised modification and manufacture

of spare parts

Modifications or alterations of the equipment supplied are only

permitted after consultation with the manufacturer. Original spare

parts and accessories authorised by the manufacturer ensure

safety. The use of other parts can invalidate any liability of the

manufacturer for resulting damage.

2.8

Unauthorised modes of operation

The warranty relating to the operating reliability and safety of the

unit supplied is only valid if the equipment is used in accordance

with its designated use (see section 4). The limits stated in the

data sheet must not be exceeded under any circumstances.

3

Transport and interim storage

The package unit is packaged on pallets or in wooden crates

and wrapped in plastic foil for shipping and interim storage. All

connecting points are capped. It is imperative that the shipping /

handling instructions shown on the package be followed.

The unit must be protected against frost.

If upon unpackaging the unit you should discover that the package

has been damaged by dropping or some other form of mechanical

impact, please carefully inspect the unit itself for possible damage

and inform the freight forwarder / KSB’s customer service, even

if you have not been able to detect any such damage.
Once the unit has been removed from the package, it must be

stored in accordance with the location and installation instructions

(see Installation and location).

4

Description

4.1

General description

The fully electronic pressure boosting package units are supplied

ready for connection.
The equipment circuitry allows both direct and indirect connection

to the water supply system.

The equipment must be operated and maintained as to ensure

uninterrupted reliability of water supply, without causing

disturbances in the public water supply or other consumer

supply systems.

Any applicable 

Water utility or fire protection regulations

 must

be complied with.
Furthermore, local conditions must be taken into account (for

example excessive or very unsteady supply pressure requiring

the installation of a pressure reducer).

4.2

Configuration and function

4.2.1 Configuration

Between 2 and 6 vertical high-pressure pumps (for description

and function, please refer to the pump’s Operating Instruction)

are arranged on a baseplate.
Each pump is seated on its own anti-vibration mounts.
The pumps are arranged in line are coupled by mild steel pipes.
On the system side, a swing check valve and a shut-off butterfly

valve are fitted downstream of each pump.
On the suction side, a ball valve or a shut-off butterfly valve are

fitted upstream of each pump as a service valve.
The shut-off elements permit dismantling of individual pumps

without having to drain the pipework. The discharge side non-

return valve ensures that the unit remains filled with water and

prevents backflow through the pumps.
Both headers feature additional connections for draining, venting

and installation of various dry running protection devices.
The accumulator is fitted with an isolating valve. It compensates

discharge-side peak pressures and together with the minimum

operating period, limits the pumps’ switching frequency.
moviBOOST VPt / CL units are started up as a function of

pressure. To this effect, a pressure transmitter is fitted in the

discharge-side piping.
Depending on the number and power of the pumps, the

completely wired control cabinet is either supplied mounted on

the baseplate or as a free-standing cabinet.
Only supplementary and special equipment is supplied fitted on

the unit.
Accessories such as expansion joints, tanks, accumulators,

pressure reducers etc. are supplied with the unit but are not

mounted.
The unit is driven by surface-cooled three-phase squirrel-cage

motors, 50 Hz, air-cooled, 2-pole, KSB standard motor with main

dimensions to IEC. Other motor makes after consultation with

KSB.
up to 2.2 kW 220-240 V/380-420 V,

from 3 kW 380-420 V/660-725 V

enclosure IP 55, thermal class F, up to 4 kW design V18,

from 5.5 kW design V1

4.2.2 Function

moviBOOST VPt / CL is started as a function of pressure and

stopped as a function of demand.

Automatic mode

Two to six pumps are controlled and monitored by a micro-

processor control unit.
Each pump is connected to a frequency inverter and controlled

by the control unit in order to ensure a constant system discharge

pressure of +0.4 bar.
As the demand increases or decreases, the peak load pumps

will be switched on and off automatically. As soon as the demand

increases after one pump has been switched off, another pump

which has not been in operation before is switched on.
After the last (PI-controlled) pump has been switched off and the

demand increases again, the next pump in line is switched on

and connected to the frequency inverter.

Содержание moviBOOST CL

Страница 1: ...ments 6 6 6 Installation altitude 6 6 7 Pollution exposure 6 6 8 Checking the voltage 6 6 9 Logic circuit diagrams 6 6 10 Over load relay 6 6 11 Potential equalization 6 Contents Sr no Description Page no 7 Commissioning start up 6 7 1 Preparations for commissioning start up 6 7 2 Test run 6 7 3 Checking the direction of rotation 7 7 4 Functional description Automatic mode 7 7 5 Starting the unit ...

Страница 2: ...rkings for fluid connections must always be complied with and be kept in a perfectly legible condition at all times 2 2 Personnel qualification and training All personnel involved in the operating maintaining servicing inspecting and installing the unit must be fully qualified to carry out the work involved Areas of responsibility and personnel monitoring must be clearly specified by the operator ...

Страница 3: ...or very unsteady supply pressure requiring the installation of a pressure reducer 4 2 Configuration and function 4 2 1 Configuration Between 2 and 6 vertical high pressure pumps for description and function please refer to the pump s Operating Instruction are arranged on a baseplate Each pump is seated on its own anti vibration mounts The pumps are arranged in line are coupled by mild steel pipes ...

Страница 4: ...ressure boosting units ordered without dry running protection the terminal intended for the dry running device is open If no dry running protection device is connected when commissioning takes place the unit will be stopped after 7 seconds If the dry running protection terminal is deactivated by means of a bridge the operator shall assume responsibility for any dry running that might occur 4 4 Man...

Страница 5: ...Shut off elements 10 Pressure transmitter 11 Pressure reading indicator 12 Control system 13 Pump with drain and vent valve 14 Non return valve NRV 15 Discharge pipe 16 Accumulator discharge pressure side 17 Pressure reducer discharge pressure side 18 Distribution line downstream of moviBOOST 19 Consumer line downstream of moviBOOST 20 By pass line for direct connection only 21 Consumer line upstr...

Страница 6: ...xpansion joints The unit must be accessible to allow maintenance and repair work 5 6 Installing a pressure reducer A length of approximately 600 mm must be provided on the inlet pressure side to accommodate a pressure reducer if necessary A pressure reducer must be installed if the inlet pressure fluctuation is so high that the unit must be stopped or if the total system pressure inlet pressure pl...

Страница 7: ...air may contain dry dust comparable to that normally encountered in work environments with no extraordinary machinery induced dust accumulation Exposure to unusually high dust levels acids corrosive gases salts etc must be avoided 6 8 Checking the voltage Compare the mains voltage with the name plate data and the control unit s circuit diagram 6 9 Logic circuit diagrams For each unit are included ...

Страница 8: ...operation each pump must be started up individually to check the direction of rotation If a pump is found to be running in the wrong direction switch two phases on the motor terminal board 7 4 Functional description Automatic mode After start up pressure boosting units in standard design will run in automatic mode For units with manual 0 automatic switch set all pumps to automatic mode Each pressu...

Страница 9: ...ter Name Line 3 Parameter Value Line 4 Alarm Line 7 5 2 Menu structure Main Screen Select Group Status No of Pumps Suction Water status Pump 1 status Pump 2 status Pump 3 status Pump 4 status Pump 5 status Pump 6 status Service Interval Sensor Pressures Settings User Level Settings Service Level Settings Factory Level Settings Information Diagnostic Active Alarms Alarm History 7 5 3 Access Level V...

Страница 10: ...rameter press 0 Number can then be entered digit by digit from left to right by numeric keys To confirm the selected value press ENTER The cursor moves to the next position second position from the left Make the settings as described above fo the subsequent positions and then save the new parameter value by pressing ENTER Press 8 repeatedly to return to the main display The new setpoint is now act...

Страница 11: ...ngs User Slave id pump4 4 3 2 2 11 Settings User Slave id pump5 5 3 2 2 11 Settings User Slave id pump6 6 3 2 2 12 Settings User Drv min freq 25 Hz 3 2 2 14 Settings User Accumultr Presr 5 0bar 3 2 2 15 Settings User Accumultr time 3 Sec 3 2 2 16 Settings User Shutoff_ presr 0 0bar 3 2 2 17 Settings User No flow time 20 Sec 3 2 2 21 Settings User Low Presur Func 0 3 2 2 22 Settings User Low presur...

Страница 12: ...ttings Service Max sensor press 16 bar 3 2 2 11 Settings Service Slave id pump1 1 3 2 2 11 Settings Service Slave id pump2 2 3 2 2 11 Settings Service Slave id pump3 3 3 2 2 11 Settings Service Slave id pump4 4 3 2 2 11 Settings Service Slave id pump5 5 3 2 2 11 Settings Service Slave id pump6 6 3 2 2 12 Settings Service Drv min freq 25 Hz 3 2 2 13 Settings Service Run chk Interval 24 Hrs 3 2 2 14...

Страница 13: ...ngs Service 7 Q H 52 5 16 4 3 2 2 49 Settings Service Set pt cmpnsatn 0 5 3 2 2 50 Settings Service Last pmp oNoFF P1OFF Line 2 Default Setting 3 2 3 1 Settings Factory No of pumps 3 3 2 3 2 Settings Factory Dry run rst Auto 3 2 3 3 Settings Factory Max start stop 50 3 2 3 4 Settings Factory Correction time 10 Sec 3 2 3 5 Settings Factory Start delay 3 Sec 3 2 3 6 Settings Factory Stop delay 2 Sec...

Страница 14: ...tory PID freq 0 0Hz 3 2 3 34 Settings Factory PID time 0 0 mSec 3 2 3 35 Settings Factory Sensor F selcn 0 3 2 3 36 Settings Factory Sensor F pmp On 1 3 2 3 37 Settings Factory Deadband 0 0 Bar 3 2 3 38 Settings Factory Rst pump data Sel 0 Press 1 0 3 2 3 39 Settings Factory Reset serv intvl PRESS 1 3 2 3 40 Settings Factory Save usrt to fact PRESS 1 3 2 3 41 Settings Factory Edit usr passwd 7353 ...

Страница 15: ... is a NC contact When this contact opens all pumps which are in operation will be sequenced out after the set delay When this contact is closed the pumps will start up again in line with the demand 7 12 Shutdown As long as the unit is out of operation water is supplied directly through the unit at inlet pressure Set master switch to 0 For prolonged shutdown drain the unit Alarm Alarm Description N...

Страница 16: ...the power supply i e all electric devices are still live even if the pumps are not in automatic operation mode Prior to working on the control cabinet or opening the motor terminal box set the master switch to 0 and unscrew the back up fuse Do not tamper with the control unit which should only be serviced by KSB s customer service Prior to opening any electric equipment such as control cabinet and...

Страница 17: ...Movitec 400 V Number of pumps motors pumps kW A 2 3 4 5 6 0202B 0 37 0 94 1 3 2 2 6 3 3 3 9 0203B 0 37 0 94 1 3 2 2 6 3 3 3 9 0204B 0 37 0 94 1 3 2 2 6 3 3 3 9 0205B 0 37 0 94 1 3 2 2 6 3 3 3 9 0206B 0 55 1 33 1 9 2 8 3 7 4 7 5 6 0207B 0 55 1 33 1 9 2 8 3 7 4 7 5 6 0208B 0 55 1 33 1 9 2 8 3 7 4 7 5 6 0209B 0 75 1 68 2 4 3 6 4 7 5 9 7 0210B 0 75 1 68 2 4 3 6 4 7 5 9 7 0211B 1 1 2 4 3 4 5 1 6 7 8 4 ...

Страница 18: ... 4 15 5 9 8 8 11 6 14 5 17 4 1503B 3 5 59 7 9 11 8 15 7 19 6 23 4 1504B 4 7 45 10 6 15 7 20 9 26 1 31 2 1505B 5 5 10 14 2 21 1 28 1 35 41 9 1506B 5 5 10 14 2 21 1 28 1 35 41 9 1507B 7 5 13 4 19 28 3 37 6 46 9 56 2 1508B 7 5 13 4 19 28 3 37 6 46 9 56 2 2502B 4 7 45 10 6 15 7 20 9 26 1 31 2 2503B 5 5 10 14 2 21 1 28 1 35 41 9 2504B 7 5 13 4 19 28 3 37 6 46 9 56 2 2505B 11 19 3 27 4 40 8 54 2 67 5 80...

Страница 19: ...0B 1 29 90B 2 2 47 90B 2 1 52 90B 2 58 90B 3 2 75 90B 3 1 81 90B 3 87 90B 4 2 105 90B 4 1 110 90B 4 117 90B 5 2 134 90B 5 1 140 90B 5 146 90B 6 2 163 Pump Shutoff head 10B 4 46 10B 5 57 10B 6 69 10B 7 80 10B 8 92 10B 9 103 10B 10 114 10B 11 126 10B 13 148 10B 15 171 10B 17 194 10B 19 217 10B 21 239 15B 1 15 15B 2 29 15B 3 43 15B 4 57 15B 5 72 15B 6 86 15B 7 100 15B 8 114 15B 9 129 15B 10 143 15B 1...

Страница 20: ... purchase order Start up pressure set too high Check setting 10 Pressure transmitter set incorrectly or Check setting 11 defective Pre charge pressure of the accu too low Restore nitrogen cushion 12 Defective accumulator Check integrity replace 13 Defective mechanical seal Replace by new one 14 Suction side pressure transmitter mano Check setting 15 metric switch set incorrectly or defective Syste...

Страница 21: ...let pressure monitoring pvor x ______________________ Value set at inlet pressure switch Stop pressure pA bar ______________ Inlet pressure pvor bar ______________ Pre charge pressure of accumulator pvor bar ______________ 4 Special information The system operator must notify the responsible water company of commissioning If in addition the system is operated with pressure vessels of groups III IV...

Страница 22: ...or switch Briefly start up each pump manually and compare the fan impeller s direction of rotation with the arrow indicating the direction of rotation 10 Check the direction of rotation in automatic mode 11 Check the start and stop pressure readjust if required 12 Test the proper function of the lack of water and dry running protection equipment If not fitted make a relevant note in the commission...

Страница 23: ...ngredients Disposal Methods 1 Pumps Paint Pump body Base frame Sludge to be disposed through authorised re processor Non ferrous parts a Impellers Diffusers b Bushes c Stage sleeves d Thrust plate To be disposed through authorized re processor e Wearing ring f Coupling Guard g Brg Guard Rubber Plastic Parts a Cover for NRV b Plastic cap To be disposed through authorized re processor c Nozzle blank...

Страница 24: ...moviBOOST VPt CL NOTES ...

Отзывы: