moviBOOST VPt / CL
10
7.8
Parameter list
Parameter No
Group
Sequence
1
Power on Screen
KSB PUMP LTd.
2
Default Screen
SYSTEMS PRESSURE
3-2-2-1
Settings-User
No of Pump
3
3-2-2-2
Settings-User
Dry run rst
Auto
3-2-2-3
Settings-User
Max start/stop
50
3-2-2-4
Settings-User
Correction time
10 Sec
3-2-2-5
Settings-User
Start delay
3 Sec
3-2-2-6
Settings-User
Stop Delay
2 Sec
3-2-2-7
Settings-User
Dry run delay
30 Sec
3-2-2-8
Settings-User
Max run time
24 Hr
3-2-2-9
Settings-User
System pressure
4.1 bar
3-2-2-10
Settings-User
Max sensor press
16 bar
3-2-2-11
Settings-User
Slave id pump1
1
3-2-2-11
Settings-User
Slave id pump2
2
3-2-2-11
Settings-User
Slave id pump3
3
3-2-2-11
Settings-User
Slave id pump4
4
3-2-2-11
Settings-User
Slave id pump5
5
3-2-2-11
Settings-User
Slave id pump6
6
3-2-2-12
Settings-User
Drv min freq
25 Hz
3-2-2-14
Settings-User
Accumultr Presr
5.0bar
3-2-2-15
Settings-User
Accumultr time
3 Sec
3-2-2-16
Settings-User
Shutoff_ presr
0.0bar
3-2-2-17
Settings-User
No flow time
20 Sec
3-2-2-21
Settings-User
Low Presur Func
0
3-2-2-22
Settings-User
Low presure SP
10.0bar
3-2-2-23
Settings-User
Low presur time
5 Sec
3-2-2-25
Settings-User
Q min max functn
0
3-2-2-26
Settings-User
Q min Q max
0.0 0.0
3-2-2-29
Settings-User
Adaptive sp func
0
3-2-2-30
Settings-User
Adapt sp
0.0 Bar
3-2-2-31
Settings-User
Frm Time 00: 00Hr
To Time 00: 00Hr
3-2-2-32
Settings-User
Set week day
2 Wednesday
2
3-2-2-35
Settings-User
Sensor F selcn
0
3-2-2-42
Settings-User
1. Q H
16.0 23.8
3-2-2-43
Settings-User
2. Q H
24.0 23.3
Line 2
Default Setting
User Level