6 Commissioning/Start-up/Shutdown
37 of 104
mini-Compacta
2317.886/16-EN
Pump LED
"High water" LED
Operation
relay/
general
fault
message
Pump
Integrated
alarm buzzer
LiveZero gone
Off
Contact 11-14
closed
Depending on
filling level
Off
Power failure:
Power failure
Contact 11-12
closed
Off
Interval tone
NOTE
If battery voltage drops below 5.3 V (Basic 1) or 10.6 V (Basic 2), the control units
automatically switch off the mains-independent alert to prevent excessive
discharging of the battery.
6.3.2 Commissioning with LevelControl Basic 2
Settings for the collecting tank
To reduce the frequency of starts the lowest open inlet nozzle can be selected at the
control unit.
1. Press the
ESC
key until the level is displayed.
2. Press the
OK
key and
ESC
key simultaneously.
ð
Parameter number 3.1.2.2 is displayed.
3. Confirm with
OK
.
ð
A digit flashes in the display.
4. Use the arrow keys to select the inlet nozzle in acc. with the table below.
5. Press
OK
.
ð
The setting has been saved.
Table 15:
Possible settings
Inlet nozzle used
Setting displayed
[mm]
180
1
250
2
320
3
700
4
Vertical
5
Connecting the rechargeable battery
DANGER
Live voltage
Danger to life!
▷
Only open the device after it has been de-energised.
Fig. 18:
Connecting the rechargeable battery (LevelControl Basic 2 BC)