6 Commissioning/Start-up/Shutdown
36 of 104
mini-Compacta
2317.886/16-EN
Fig. 17:
Connecting a fault signalling contact
6.3.1.1.3 Acknowledging alerts
NOTE
Displayed alerts can be acknowledged by pressing this key. The integrated alarm
buzzer will be muted.
The alert message disappears as soon as the cause of the alert has gone.
Alarms can be acknowledged by pressing the
OK
key on the front of the control unit.
6.3.1.1.4 Messages and faults
Table 14:
Messages
Pump LED
"High water" LED
Operation
relay/
general
fault
message
Pump
Integrated
alarm buzzer
Operation:
Pump OFF
Off
Off
Pump running
Steady green
Contact 11-14
closed
On
TCB - Excessive motor temperature
TCB fault
(unacknowledged)
Flashing red
Contact 11-12
closed
Off
Interval tone
TCB fault
(acknowledged)
Steady red
Contact 11-12
closed
Off
Off
TCB fault gone
(unacknowledged)
Flashing red
Contact 11-14
closed
Depending on
filling level
Interval tone
TCB fault gone
(acknowledged)
Off
Contact 11-14
closed
Depending on
filling level
Off
High water:
High water
(unacknowledged)
Flashing red
Contact 11-12
closed
On
Interval tone
High water
(acknowledged)
Steady red
Contact 11-12
closed
On
Off
High water
gone
Off
Contact 11-14
closed
Depending on
filling level
Off
External fault:
External fault
(unacknowledged)
Flashing red
Contact 11-12
closed
On or Off
Interval tone
External fault
(acknowledged)
Steady red
Contact 11-12
closed
On or Off
Off
External fault
gone
Off
Contact 11-14
closed
On or Off
Off
LiveZero – Broken wire detection:
LiveZero
(unacknowledged)
Flashing red
Contact 11-12
closed
Off
Interval tone
LiveZero
(acknowledged)
Steady red
Contact 11-12
closed
Off
Off