Pump Switchgear / Control Systems

LevelControl Control Units

18

LevelControl Basic 2

4041.5/12-EN

LevelControl Basic 2 for Amarex / Amarex N

Non-ATEX-compliant versions

Documented device versions

Control units for single-pump station, non-ATEX-compliant

Size

Float switch 

incl. 4-20 mA input

Pneumatic

Bubbler control

DFNO

DPNO

DLNO in BS housing

DLNO in BC housing

400 V: 2,5 - 4,0 A

BC1 400 

DFNO

 040

BC1 400 

DPNO

 040

BS1 400 

DLNO

 040

BC1 400 

DLNO

 040

400 V: 4,0 - 6,3 A

BC1 400 

DFNO

 063

BC1 400

 DPNO

 063

BS1 400 

DLNO

 063

BC1 400 

DLNO

 063

400 V: 6,3 - 10 A

BC1 400

 DFNO

 100

BC1 400

 DPNO

 100

BS1 400 

DLNO

 100

BC1 400 

DLNO

 100

Control units for dual-pump station, non-ATEX-compliant

Size

Float switch 

incl. 4-20 mA input

Pneumatic

Bubbler control

DFNO

DPNO

DLNO in BS housing

DLNO in BC housing

400 V: 2,5 - 4,0 A

BC2 400 

DFNO

 040

BC2 400 

DPNO

 040

BS2 400 

DLNO

 040

BC2 400 

DLNO

 040

400 V: 4,0 - 6,3 A

BC2 400 

DFNO

 063

BC2 400

 DPNO

 063

BS2 400 

DLNO

 063

BC2 400 

DLNO

 063

400 V: 6,3 - 10 A

BC2 400

 DFNO

 100

BC2 400

 DPNO

 100

BS2 400 

DLNO

 100

BC2 400 

DLNO

 100

Functional comparison

Symbols key

Symbol

Description

d

Digital display of switching points

o

Optional

Control unit feature

-

Not a control unit feature

Comparison of functions of Amarex / Amarex N single-pump stations and dual-pump stations, non-ATEX-compliant version

Feature

Single-pump station

Dual-pump station

DFNO

DPNO

DLNO

(BS

housing)

DLNO

(BC

housing)

DFNO

DPNO

DLNO

(BS

housing)

DLNO

(BC

housing)

Functions

Draining

Filling using float switch(es)

-

-

-

-

-

-

Stand-by pump: 1 pump redundant

-

Pump changeover after each start

-

Pump changeover in event of fault

-

Peak load operation function

-

Runtime limitation

OFF via after-run time

OFF via level

Functional check run after idle period

Alert history

Display and operation

7-segment display

Indication of water level

d

d

Operation / fault / pump running
(displayed for each pump)

Multicolour LED

Multicolour LED

General fault (traffic light)

LED

LED

High water

LED

LED

Mains voltage

Operating hours of each pump

Starts per pump

Rotary field recognition of mains power
supply

Phase monitoring

Содержание LevelControl Basic 2

Страница 1: ...Level Control Unit LevelControl Basic 2 Type Series Booklet...

Страница 2: ...herein must neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without the manufacturer s expres...

Страница 3: ...riants 4 Designation 5 Product benefits 6 Selection information 6 Technical data 7 Dimensions and weights 8 LevelControl Basic 2 for Ama Drainer 9 LevelControl Basic 2 for Ama Porter 14 LevelControl B...

Страница 4: ...Basic 2 included in the scope of supply in some cases mini Compacta Compacta LevelControl Basic 2 included in the scope of supply Sewatec Sewabloc Etaline Etanorm Etabloc Other pumps on request Varian...

Страница 5: ...rement 3 5 m M Pneumatic level measurement 10 5 m L Bubbler control 2 m H Bubbler control 3 m U Analog input 4 20 mA V Voltage input 0 5 4 5 V D Digital level switch N ATEX N Without ATEX functions E...

Страница 6: ...htning protection concept must be provided by the operator or by a suitable provider commissioned by the operator Surge protective devices can be found in the extended accessories range type series bo...

Страница 7: ...ety barriers type Stahl 9002 13 280 093 001 For ATEX with digital level switches selected via KSB EasySelect ATEX compliant versions in BS housing Single pump station incl 3 intrinsic safety barriers...

Страница 8: ...is fully discharged Dimensions and weights Dimensions and weights Type Nominal current per pump H W D kg max A mm BC 10 400 281 135 4 5 4 7 BS1 10 400 300 155 12 BS15 10 600 400 200 12 BS1 14 600 400...

Страница 9: ...00 DPNO 063 400 V 6 3 10 A BC2 400 DFNO 100 BC2 400 DPNO 100 400 V 13 18 A BS2 400 SFNO 180 BS2 400 SPNO 180 Functional comparison Symbols key Symbol Description d Digital display of switching points...

Страница 10: ...230 V AC Ama Drainer N 301 302 303 Ama Drainer N 358 Ama Drainer NE 4 5 bimetal switch in the motor The bimetal switch is not connected to the control unit 3 400 V AC Ama Drainer ND 4 5 Ama Drainer B...

Страница 11: ...D 014 015 Analog IN 24V PE gn ye PE gn ye 29 28 J203 Alarm 29 Fig 1 Circuit diagram Ama Drainer N 301 302 303 Ama Drainer N 358 Ama Drainer NE 4 5 Ama Porter NE 1 Contactor pump 1 16 Pump 2 2 Contacto...

Страница 12: ...24V GND 014 015 Analog IN 24V 28 J203 Alarm 30 30 Fig 2 Circuit diagram Ama Drainer ND 4 5 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 3 400 V 1 230 V 18 High...

Страница 13: ...Analog IN 24V 28 J203 Alarm 30 30 Fig 3 Circuit diagram Ama Drainer B 80 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 3 400 V 1 230 V 18 High water float switch...

Страница 14: ...00 DFNO 063 BC2 400 DPNO 063 BS2 400 DLNO 063 BC2 400 DLNO 063 Functional comparison Symbols key Symbol Description d Digital display of switching points o Optional Control unit feature Not a control...

Страница 15: ...mal circuit breaker bimetal Optional components Rechargeable battery for powering the device o o Control cabinet heating for type BS o Alarm equipment 1 free alarm input 1 digital input for high water...

Страница 16: ...4 015 Analog IN 24V PE gn ye PE gn ye 29 28 J203 Alarm 29 Fig 4 Circuit diagram Ama Porter NE 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 18 High water float sw...

Страница 17: ...24V PE gn ye 30 28 J203 Alarm 30 Fig 5 Circuit diagram Ama Porter ND 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 18 High water float switch 4 Leakage monitor 1...

Страница 18: ...LNO 063 BC2 400 DLNO 063 400 V 6 3 10 A BC2 400 DFNO 100 BC2 400 DPNO 100 BS2 400 DLNO 100 BC2 400 DLNO 100 Functional comparison Symbols key Symbol Description d Digital display of switching points o...

Страница 19: ...circuit breaker bimetal Motor leakage moisture monitoring Optional components Rechargeable battery for powering the device o o Control cabinet heating for type BS o o Alarm equipment 1 free alarm inp...

Страница 20: ...040 BS2 400 DLEO 040 BC2 400 DLEO 040 400 V 4 0 6 3 A BS2 400 DFEO 063 BC2 400 DPEO 063 BS2 400 DLEO 063 BC2 400 DLEO 063 400 V 6 3 10 A BS2 400 DFEO 100 BC2 400 DPEO 100 BS2 400 DLEO 100 BC2 400 DLE...

Страница 21: ...aker bimetal Motor leakage moisture monitoring Optional components Rechargeable battery for powering the device o o Control cabinet heating for type BS o o o o Alarm equipment 1 free alarm input non A...

Страница 22: ...GND 014 015 Analog IN 24V 5 4 5 4 PE 6 6 6 9 M 3 1 2 3 5 21 4 20 PE 6 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 22 24 25 26 27 28 J203 Alarm 30 30 Fig 6 Circuit diagram Amarex 1 Co...

Страница 23: ...6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 22 24 25 26 27 28 J203 Alarm 30 30 Fig 7 Circuit diagram Amarex N 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections...

Страница 24: ...DFNO 100 BS2 400 DFEO 100 BS2 400 DPEO 100 BS2 400 DLEO 100 400 V 9 14 A BS2 400 SFNO 140 BS2 400 SFEO 140 BS2 400 SPEO 140 BS2 400 SLEO 140 400 V 13 18 A BS2 400 SFNO 180 BS2 400 SFEO 180 BS2 400 SPE...

Страница 25: ...nitoring Optional components Rechargeable battery for powering the device o o Additional intrinsic safety barrier o o o o o o Control cabinet heating o o Alarm equipment 1 free alarm input 1 digital i...

Страница 26: ...012 013 014 015 010 011 019 014 015 Analog IN 24V GND 014 015 Analog IN 24V 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 22 24 25 26 27 28 J203 Alarm 20 21 9 M 3 1 2 3 PE T PTC Relais 10 11 16...

Страница 27: ...rmal circuit breaker 19 Float switch 6 Release 20 Digital switch 7 Volt free alarm contact 21 Analog sensor 4 20 mA 8 Float switch digital switch 22 Peak load ON 9 High water float switch 23 Pump ON O...

Страница 28: ...or pump 1 9 Mains supply 4 Connection for pump 2 10 Contactors 5 Manual 0 automatic switch 11 Motor protection switch pumps 6 Control board 12 Rechargeable battery optional Type BC2 400 DFNO 010 100 3...

Страница 29: ...p connection 5 Internal pressure sensor 11 Motor protection switch pumps 6 Pneumatic 12 V for horn etc 12 Rechargeable battery optional Type BS2 400 DLNO 010 100 BS2 400 DLEO 010 100 3 400 V AC DOL st...

Страница 30: ...ersion 1 2 3 9 10 13 4 6 5 7 8 12 11 1 Master switch 7 Digital inputs 4 20 mA 12 V for horn etc 2 Control panel 8 Contactors pump connection 3 Manual 0 automatic switch 9 Mains supply 4 Control transf...

Страница 31: ...arger than usual LevelControl Basic 2 for outdoor installation Type BC Using a heater is recommended Type BS A heater must be used Overview of outdoor cabinets Control unit Material enclosure control...

Страница 32: ...f base H W D mm 900 780 315 IP44 glass fibre reinforced polyester colour RAL 7035 locking device profile half cylinder suitable for buried installation including metal frame for setting in concrete 19...

Страница 33: ...Description Mat No kg O210 Pump current measuring module Can only be used in combination with signalling module Measuring range 0 5 10 A 15 A 19075188 0 15 O211 Measuring range 10 20 A 30 A 19075189 0...

Страница 34: ...in a pump sump above the pump start up point Warning at a water level of 1 mm in areas with a flooding or leakage risk e g in the cellar or next to the washing machine in the kitchen or bathroom Dimen...

Страница 35: ...0 155 Operating manual in Russian13 01149725 0 155 Operating manual in Hungarian13 01148344 0 155 Operating manual in Turkish13 01235989 0 155 Operating manual in Bulgarian13 01350442 0 155 Operating...

Страница 36: ......

Страница 37: ......

Страница 38: ...KSB SE Co KGaA Johann Klein Stra e 9 67227 Frankenthal Germany Tel 49 6233 86 0 www ksb com 4041 5 12 EN 28 01 2021...

Отзывы: