Pump Switchgear / Control Systems
LevelControl Control Units
31
LevelControl Basic 2
4041.5/12-EN
Overview of outdoor cabinets
Enclosure IP44 = protection against splashing water.
Ventilation via ventilation ducts to prevent condensation.
The ventilation ducts are designed as a labyrinth to prevent the ingress of foreign bodies and are poke proof.
To prevent condensation inside the housing, grout the foundation up to the height of the cable fixing rail after installation.
LevelControl Basic 2 for 230 V is designed with sockets on the side wall (connection of the pump/s).
To make sure the connections can be made at the plugs, outdoor cabinets for this version are selected one size larger than usual.
LevelControl Basic 2 for outdoor installation:
Type BC: Using a heater is recommended.
Type BS: A heater must be used.
Overview of outdoor cabinets
Control unit
Material, enclosure
control unit
Dimensions
Outdoor cabinet / wall-
mounted cabinet
Item
Installation
H × W × D
[mm]
BC1 010/016/025/040/063/100
BC2 010/016/025/040/063/100
Plastic, IP54
400 × 281 × 135
Outdoor cabinet type 142,
IP44
O10
Suitable for
buried
installation
BS1 010/016/025/040/063/100/140/
180/230/250
BS2 010/016/025/040/063/100
Sheet steel, IP54
400 × 300 × 155
600 × 400 × 200
Outdoor cabinet type 0/845,
IP44
O11
Suitable for
buried
installation
BS1 400/630
BS2 140/180/230/250/400/630
Sheet steel, IP54
800 × 600 × 200
Outdoor cabinet type 1/1005,
IP44
O12
Suitable for
buried
installation
BC1 010/016/025/040/063/100
BC2 010/016/025/040/063/100
Plastic, IP54
400 × 281 × 135
Wall-mounted cabinet KS
O14
Wall-mounted
model