6 Commissioning/Start-up/Shutdown
30 of 64
Hya-Rain/Hya-Rain N
6.2 Operating limits
6.2.1 Ambient conditions
Observe the following parameters and values during operation:
Table 9:
Permissible ambient conditions
Ambient condition
Value
Ambient temperature
+40 °C maximum
Atmospheric humidity
50 % maximum at 40 °C
6.2.2 Maximum operating pressure
CAUTION
Permissible operating pressure exceeded
Damage to connections and seals!
▷
Never exceed the operating pressure specified in the data sheet.
The maximum operating pressure is 6 bar.
6.2.3 Fluid handled
6.2.3.1 Permissible fluids to be handled
▪
Service water
▪
Rainwater (not containing abrasive substances)
6.2.3.2 Fluid temperature
Maximum fluid temperature: 35 °C