6 Commissioning/Start-up/Shutdown
29 of 64
Hya-Rain/Hya-Rain N
6.1.3 Start-up
Hya-Rain
ü
The power plug has been plugged into the socket.
1. Set the master switch to 1. (
ð
The pump control unit controls the system automatically:
▪
When a consumer installation is opened, the pump set starts up.
▪
When all consumer installations are closed, the pump set stops.
Table 7:
Description of indicator lamps
Lamp
Description
Green
Ready for operation
Red
Lack of water: Dry running protection stops the pump set.
Fault: A fault can be reset by pressing the reset key. When the reset key
is pressed and held down, the system is in manual mode.
Hya-Rain N
ü
The power plug has been plugged into the socket.
1. Set the master switch to 1. (
2. Calibrate the level display. (
6.1.4 Functional test
Dry running protection
ü
The system has been properly set up, installed, connected and commissioned.
1. Close the suction-side inlet of the rainwater storage tank.
ð
No flow. The pump control unit stops the pump set after an after-run time of
approx. 10 seconds.
2. If necessary, repeat the after-run time by pressing the reset key.
Operating modes
ü
The system has been properly set up, installed, connected and commissioned.
1. Check the indicator lamps:
Table 8:
Indicator lamps for operating modes
Operating mode
Symbol
Indicator lamp
Automatic mode
This indicator lamp lights up when the pump automatically switches to the
available water tank.
Mains water mode
This indicator lamp lights up when the pump withdraws water from the
mains water storage tank and the mains water back-up system is activated.
Rainwater storage tank
This indicator lamp lights up when the pump withdraws water from the
rainwater storage tank.