24
AMTRONIC R1300
Case N
°
2:
- ACTAIR 3 to 200, end-stops on opening
- ACTAIR NG 2 to 160, end-stops on opening
- DYNACTAIR 1.5 to 25, opening by air failure, end-stops on opening
- DYNACTAIR 50 and 100, closing by air failure, end-stops on closing
- DYNACTAIR NG 1 to 80, closing by air failure, end-stops on closing
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
Last command
Open
Closed
VII - 3 4/3 distributor
The solenoid valve action depends on the valve safety position when the device has no electrical supply and for the
type of actuator in application.
Case N
°
1:
- ACTAIR 3 to 200, end-stops on closing
- ACTAIR NG 2 to 160, end-stops on closing
- DYNACTAIR 1.5 to 25, closing by air failure, end-stops on closing
- DYNACTAIR 50 and 100, opening by air failure, end-stops on opening
- DYNACTAIR NG 1 to 80, opening by air failure, end-stops on opening
Safety position on loss of
electrical supply
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
EV1=1
EV2=1
STOP
(stays in position)
STOP
(stays in position)
Closed
Open
Closed
Closed
STOP
(stays in position)
Open
Open
Open
STOP
(stays in position)
Closed
Case N
°
2:
- ACTAIR 3 to 200, end-stops on opening
- ACTAIR NG 2 to 160, end-stops on opening
- DYNACTAIR 1.5 to 25, opening by air failure, end-stops on opening
- DYNACTAIR 50 and 100, closing by air failure, end-stops on closing
- DYNACTAIR NG 1 to 80, closing by air failure, end-stops on closing
Safety position on loss of
electrical supply
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
EV1=1
EV2=1
STOP
(stays in position)
STOP
(stays in position)
Open
Closed
Closed
Closed
STOP
(stays in position)
Open
Open
Open
STOP
(stays en position)
Closed
Содержание AMTRONIC R1300