AMTRONIC R1300
Distributor - Solenoid valve unit
Adjustment screw R2
Adjustment
screw R1
ACTAIR 3 to 200 and ACTAIR NG 2 to 160
R1
R2
Stop on closing (standard version)
Closing time
Opening time
Stop on opening (upon request)
Opening time
Closing time
DYNACTAIR 1.5 to 100 and
DYNACTAIR NG 1 to 80
Safety position on loss of
pneumatic supply
R1
R2
DYNACTAIR 1.5 to 25
Closed
Closing time
Opening time
DYNACTAIR 50 and 100
Open
DYNACTAIR NG 1 to 80
Open
DYNACTAIR 1.5 to 25
Open
Opening time
Closing time
DYNACTAIR 50 and 100
Closed
DYNACTAIR NG 1 to 80
Closed
VI - Electric connections
VI - 1 General
L’AMTRONIC is shipped with 2 IP67 plugs
- Use of cable glands:
To access the electrical connection terminals,
unscrew the 4 TORX screws (T20) from the
connection housing.
Tightening torque: 2Nm
Cable gland (option):
- 2 M 20 plastic cable glands (polyamide) for cable ø 6 to 12,
- 2 M 20 metallic cable glands (nickel- plated brass) for cable ø 7 to 12.
Connection on unpluggable connector:
- Length to be stripped: 7 mm
- Cross- section of rigid or flexible conductor: 0.14mm
2
to 1.5 mm
2
- Cross- section of flexible conductor with end connector without insulating entry cone: 0.25 mm
2
to 1.5 mm
2
- Cross- section of flexible conductor with end connector with insulating entry cone: 0.25 mm
2
to 0.5 mm
2