17
AMTRONIC R1300
VI - 2 Solenoid valve connection
Monostable distributor: only connect to EV1 solenoid valve
4/3 and bistable distributor: connect the EV1 and EV2 solenoid valves
EV1
EV2
To understand the EV1 and EV2 solenoid valves, refer to chapter VII - Pneumatic distribution.
- Electrical characteristics:
Function
Nominal voltage
Nominal power
Inrush current
3/2 NC
24 VDC
1 W
40 mA
3/2 NC
24 VAC
1 W
118 mA
3/2 NC
48 VAC
1 W
38,5 mA
3/2 NC
110 VAC
1 W
23 mA
3/2 NC
230 VAC
1 W
9 mA
3/2 NO
24 VDC
2 W
80 mA
The U pilot operating voltage tolerance is nominal - 15% and + 10%.
The stated current values are given to
10%.