7 Technical data
Mains voltage:
110/120 V AC, -15/+10%, 50/60 Hz,
220/240 V AC, -15/+10%, 50/60 Hz,
24 V DC, ±20%.
Power consumption:
10 VA for 110/120 V AC and 220/240 V AC, 1.2 W for 24 V DC.
Ambient temperature:
-15 to +60°C (+5 to +140°F), no condensation permitted. Screw
terminals 2.5 mm
2
.
Fusing:
fine-wire fuse 5 A, slow-acting, H pursuant to IEC 127, also
protects the valve outputs and external operating signal.
The input current at terminal 1 must not exceed 5 A. External
operating signal:
with mains voltage, max. 5 A resistive load
(UL listed: 5 A for 120 V),
External fault signal:
fault signalling contact, max. 5 A for 264 V.
Reset:
using a button on the device. Remote
reset:
by applying mains voltage.
Number of operating cycles:
Relay outputs: 250,000 pursuant to EN 298,
Reset button: 1000.
Housing made of impact-resistant plastic.
TC 1
–
3
For natural gas, town gas and LPG (gaseous), also for biologi-
cally produced methane.
Inlet pressure p
u
: 10 to 500 mbar (3.9 to 195 "WC). Test
period t
P
: 10 to 60 s, adjustable.
Set at the factory to 10 s.
TC 3: power consumption of the installed valves during the
opening time t
L
: max. 9.5 VA (W).
Enclosure: IP 54.
Standard coupler plug to DIN 43650/ISO 4400. Weight:
TC 1: 550 g (1.21 lbs).
TC 2: 900 g (1.98 lbs).
TC 3: 1500 g (3.31 lbs).
TC 4
Gas type and inlet pressure p
u
: dependent
on external pressure switch.
The pressure switch is set to half the inlet pressure p
u
/2. The
switching differential may not exceed ±10% of the set switching
pressure, see page 38 (External pressure switch for TC 4).
Test period t
P
:
TC 410-1: 10 to 60 s, adjustable. Set
at the factory to 10 s.
TC 410-10: 100 to 600 s, adjustable. Set
at the factory to 100 s.
Enclosure: IP 40.
External fault signal:
signalling contact (not internally fused),
max. 1 A for 264 V, max. 2 A for 120 V. Lower
section with connection terminals.
5 knock-out holes for M16 plastic cable glands. Weight:
approx. 400 g (0.88 lbs).