![krom schroeder TC Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/krom-schroeder/tc/tc_technical-information_2004666027.webp)
TC · Edition 07.14
28
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี
70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร
: 02-888-3472
โทร
:
ออกแบ
บ
:
08-08-170-170
แฟกซ์
: 02-888-3258
https://www.add-furnace.com E-mail:
3 .3 .2 Testing after burner run: Mode 2
If the jumper is set to Mode 2, the tightness test after
burner run begins as soon as the burner is switched off.
To ensure that the valves are checked for tightness once
before starting up the system, the tightness test runs when
the voltage L1 is applied. If the valves are tight, the green
OK LED lights up. The OK enable signal is not forwarded
to the automatic burner control unit until the start-up
signal has been applied.
Once the start-
switched off, the
tightness test after burner run begins. The OK enable signal
is not forwarded to the automatic burner control unit
again until the start-
If the tightness control TC detects a leak on one of the
two valves, the red LED lights up for a fault on valve V1
1
or valve V2
2
. A fault is signalled externally , e.g.
by switching on a buzzer or a warning light.
MODE 1 2
: "
TEST
"
1 L1 (+)
5
TEST
OK
1
2
6
OK
7
tp
tp
t
V1 leaking
V2 leaking
1 L1 (+)
5
TEST
OK
1
2
6
OK
7
tp
t