Expert – Checklist for commissioning
P09 Outside temperature frost protection
P09 = ----: Frost protection is deactivated.
P09 = -15.0 to +5.0 °C: When the outside temperature drops be-
low the set value, the heatcircuit controller switches the heatcircuit
pumps on.
P10 Integral control section
Integral component for the flow temperature. Enter a time here. If the
room does not reach the required temperature in the time set (from
the start of heating), the flow temperature is gradually increased until
it is sufficient to reach the desired room temperature.
P10 = ----: Function deactivated.
P10 = 3:00 h – 0:15 min: Time to reach desired room temperature
after start of heating time.
P11 Transparent Slave Parameter 01
Setting for internal parameter 01 for heat source.
P11 = -255–255: The values are only accepted by the heat source
if they are within this range.
P12 Transparent Slave Parameter 02
Setting for internal parameter 02 for heat source.
P12 = -255–255: The values are only accepted by the heat source
if they are within this range.
P1 Software version and index (62.00)
P13 = 62.00–62.99:
62 = software number
00–99 = software index
▷
If you have questions about your remote control, always specify
the software version.
Expert – Checklist for commissioning
❑
Remote control properly wired? See page 18 (Electrical socket
connection).
❑
Are the sensors required for the application connected? Sensors
that are not required are not connected.
❑
User parameters configured? Set at least time and day of the
week, see page 13 (User – Set parameters).
❑
Expert parameters configured? See page 18 (Expert – Set
parameters).
❑
Sensors tested for plausible values? See page 7 (Display
actual temperatures).
❑
Operating mode set? See page 7 (Set operating mode).
❑
Selector switch turned to
?