When displaying the actual values on the remote control, you
realise that the indicated value does not match the real one. For
example, the actual hot water temperature is 20 °C, but the
display shows 65 °C (or vice versa).
!
An incorrect sensor is connected.
•
Only use sensors with identical characteristic curves.
?
The hot water stays cold during summer mode.
!
Parameter 04 = 03 set (hot water 1 h before heating)
•
Set P04 = 01 or 02.
Should the actions described above fail to help, please
contact your heating engineer.
▷
Please have ready the software version (parameter P13).
Technical data
Voltage supply via BUS 15–18 V DC
Bus communication: OpenTherm
Protection class according to DIN EN 60529: IP 40
Protection class according to DIN EN 60730: III
Reserve power of clock: >10 h.
Permissible ambient temperature during operation: 0 to 50 °C
Permissible ambient temperature during storage: -20 to 60 °C
Permissible relative humidity, not condensing: 95 % r. H.
Sensor resistances: NTC 5 kΩ (AF),
Tolerance in ohms: ±1 % at 25 °C,
Temperature tolerance: ±0.2 °K at 25 °C.