![KROHNE OPTIWAVE-M 7400 C Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/krohne/optiwave-m-7400-c/optiwave-m-7400-c_short-manual_2004348046.webp)
46
02/2019 - MA OPTIWAVE-M 7400 C R01 en
4
OPERATION
OPTIWAVE-M 7400 C
Menu
No.
Function
Function description
Selection list
Marine Default
C1.7
Antenna Type
The type of antenna attached to the device. If
you change the antenna, this setting will have
an effect on C1.2 Tank Height and C1.5 Blocking
Distance.
Minimum access level to change the
setting: Expert
Metallic Horn (DN40),
Metallic Horn (DN50),
Metallic Horn (DN65),
Metallic Horn,(DN80),
Metallic Horn (DN100),
Metallic Horn (DN200),
Drop (PTFE, DN80), Drop
(PTFE, DN100), Drop (PTFE,
DN150), Drop (PEEK,
DN80), Drop (PEEK,
DN100), Drop
(PEEK, DN150), Hygienic
(PEEK, DN50)
DN10 PTFE
DROP antenna
C1.8
Antenna
Extension
Optional antenna extension. These are attached
between the flange and the antenna. Each
segment is 105 mm / 4.1
¨
long.
min-max:
0.0
…
1050 mm /
0.0...41.339
¨
/
0.0. 3.4449 ft
105mm
Minimum access level to change the
setting: Expert
C1.9
Distance piece
Optional distance piece between the converter
and the process connection. This
min-max:
0.0
…
2000 mm /
0 mm / 0
¨
1
is for the high-temperature version of the
0.0...78.740
¨
/
device. Each segment is 105 mm / 4.1
¨
long.
0.0. 6.5617 ft
Minimum access level to change the
setting: Expert
C1.10
Reference
Offset
Offset relating to a reference location
(distance). This value is positive when the
reference location is above the device flange
face and negative if below.
Minimum access level to change the
min-max:
-5000.0+0
…
+5000.0 m /
-196.85
+03
...+196.85
+03
¨
/
-16404...+16404 ft
0 m / 0 ft
setting: Expert
C1.11
Tank Bottom
Offset
Offset relating to a reference location (level).
The device reference point for this parameter
is the bottom of the tank (set in menu item
C1.2 Tank Height). This value is positive when
the reference location is below the tank bottom
and negative if above.
min-max:
-5000.0+0
…
+5000.0 m /
-196.85
+03
...+196.85
+03
¨
/
-16404...+16404 ft
0 m / 0 ft
Minimum access level to change the
setting: Expert
C2 Process
C2.1
Tracking
Velocity
This menu item sets the maximum rate of
change of level in metres per minute or feet per
minute. The measured value cannot change
faster than the tracking velocity.
Minimum access level to change the
setting: Expert
min-max:
1.2
-03
…
60.0 m/min /
3.94
-03 ....
196.85 ft
500
-03
m/min /
1.64042 ft/min
C2.2
Epsilon R
Product
The device automatically calculates the level
based on the product
ε
r
. If you select "TBF Full"
or "TBF Auto" in menu item C2.4 Measuring
Mode, you can change this value manually to
adjust readings.
Minimum access level to change the
setting: Expert
1.1...20
2.0