INSTALLATION
3
25
OPTIWAVE 6300 C
www.krohne.com
04/2011 - 4000305604 - TD OPTIWAVE 6300 R04 en
More than 1 FMCW radar level meter can be operated in a silo.
If possible, do not install a nozzle on the silo centerline.
If it is necessary to measure to the bottom of the silo, a 2
°
slanted flange option is available for
all antennas. For more data, refer to Installation recommendations for solids on page 26
.
Do not put the device near to the product inlet. If the product that enters the silo touches the
antenna, the device will measure incorrectly. If the product fills the silo directly below the
antenna, the device will also measure incorrectly.
Figure 3-2: Product inlets
1
The device is in the correct position.
2
The device is too near to the product inlet.
Figure 3-3: More than 1 FMCW radar level meter can be operated in a silo