TECHNICAL DATA
2
11
OPTIWAVE 6300 C
www.krohne.com
04/2011 - 4000305604 - TD OPTIWAVE 6300 R04 en
Physical layer types
Standard power signaling, bus powered, non I.S.
Other features
Bus interface with integrated reverse polarity protection
Device power supply (24 V input)
18...30 VDC
Bus power supply
9...32 VDC (non-Ex); 9...17.5 VDC (intrinsically-safe)
Basic current
20 mA
Maximum error current
20 mA
Start current after 10 ms
20 mA
Polarity sensitivity
Yes
Minimum cycle time
100 ms
Output data
Level, distance, level conversion, level mass, reflection, ullage conversion or
distance mass
Input data
None
Error current FDE
Typically 0 mA (FDE =Fault Disconnection Electronic)
Link Master function
Not supported
Approvals and certification
CE
This device fulfils the statutory requirements of the EC directives. The
manufacturer certifies successful testing of the product by applying the CE mark.
Explosion protection
Explosion protection
Explosion protection
Explosion protection
ATEX
KEMA 04ATEX1218 X
II 1 G, 1/2 G, 2 G Ex ia IIC T6...T3;
II 1 D, 1/2 D, 2 D Ex iaD 20 or Ex iaD 20/21 or Ex iaD 21 IP6X T70
°
C...T95
°
C;
II 1/2 G, 2 G Ex d[ia] IIC T6...T3;
II 1/2 D, 2 D Ex tD[iaD] A21/20 or Ex tD[iaD] A21 IP6X T70
°
C...T95
°
C
IECEx
IECEx KEM 06.0025 X
Ga Ex ia IIC T6
…
T3; Ex iaD 20 IP6X T70
°
C
…
T95
°
C;
Ga/Gb Ex d[ia] IIC T6
…
T3; Ex tD[iaD] A21/20 IP6X T70
°
C
…
T95
°
C
FM - Dual Seal-approved
NEC 500
NEC 500
NEC 500
NEC 500
XP-IS / Cl. I, Div. 1 / Gr. ABCD / T6;
DIP / Cl. II/III / Div. 1 / Gr. EFG / T6;
IS / Cl. I/II/III / Div. 1 / Gr. ABCDEFG / T6;
NI / Cl. I / Div. 2 / Gr. ABCD / T6
NEC 505
NEC 505
NEC 505
NEC 505
Cl. I / Zone 0 / AEx d[ia] IIC T6;
Cl. I / Zone 0 / AEx ia IIC T6;
Cl. I / Zone 2 / AEx nA[ia] IIC T6
Hazardous (Classified) Locations, indoor/outdoor Type 4X and 6P, IP66, Dual Seal
CSA - Dual Seal-approved
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
CEC Section 18 (Zone ratings)
Cl. I, Zone 1, Ex d, IIC (Antenna: Zone 0) T6;
Cl. I, Zone 0, Ex ia, IIC T6;
Cl. I, Zone 2, Ex nA, IIC T6
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
CEC Section 18 and Annex J (Division ratings)
XP-IS, Cl. I, Div. 2, Gr. ABCD; Cl. II, Div. 2, Gr. FG; Cl. III, Div. 2 T6;
IS, Cl. I, Div. 1, Gr. ABCD; Cl. II, Gr. FG; Cl. III T6