18
5 Connecting to power supply
OPTISWITCH 5100 C, 5150 C • Contactless electronic switch
30428-EN-210701
20-250V AC/DC
max 400mA
A
B
L
N
L
N
1
2
0,5 g / cm3
0,7 g / cm3
+
+
1
2
1 2
SW E60C
3
5
1
2
4
Fig. 9: Electronics and connection compartment, single chamber housing
1 Control lamp
2 DIL switch for mode adjustment
3 DIL switch for switching point adaptation
4 Ground terminal
5 Connection terminals
We recommend connecting OPTISWITCH 5100 C, 5150 C in such a
way that the switching circuit is open when there is a level signal, line
break or failure (safe state).
Information:
The contactless electronic switch is always shown in non-operative
condition.
Warning:
The instrument must not be operated without an intermediately
connected load, because the electronics would be destroyed if con-
nected directly to the mains. It is not suitable for connection to low
voltage PLC inputs.
Examples for typical applications:
•
Load resistance at 24 V DC: 88 … 1800 Ω
•
Rated power, relay 253 V AC: > 2.5 VA
•
Rated power, relay 24 V AC: > 0.5 VA
For direct control of relays, contactors, magnet valves, warning lights,
horns etc.
Domestic current is temporarily lowered below 1 mA after switching
off the load so that contactors, whose holding current is lower than
the constant domestic current of the electronics, are reliably switched
off.
Electronics and connec-
tion compartment
Wiring plan