10
4 Mounting
OPTISOUND 3010 C • Four-wire 4 … 20 mA/HART
30504-EN-220310
4 Mounting
4.1 General instructions
Select an installation position you can easily reach for mounting and
connecting as well as later retrofitting of a display and adjustment
module. The housing can be rotated by 330° without the use of any
tools. You can also install the display and adjustment module in four
different positions (each displaced by 90°).
Use the recommended cables (see chapter "
Connecting to power
supply
") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable gland. Rain and condensation water can thus drain off. This
applies mainly to outdoor mounting as well as installation in areas
where high humidity is expected (e.g. through cleaning processes) or
on cooled or heated vessels.
To maintain the housing protection, make sure that the housing lid is
closed during operation and locked, if necessary.
Fig. 2: Measures against moisture ingress
Metric threads
In the case of instrument housings with metric thread, the cable
glands are screwed in at the factory. They are sealed with plastic
plugs as transport protection.
You have to remove these plugs before electrical connection.
NPT thread
In the case of instrument housings with self-sealing NPT threads, it is
not possible to have the cable entries screwed in at the factory. The
free openings for the cable glands are therefore covered with red dust
protection caps as transport protection.
Prior to setup you have to replace these protective caps with ap-
proved cable glands or close the openings with suitable blind plugs.
The reference plane for the measuring range is the lower edge of the
transducer.
Installation position
Moisture
Cable entries - NPT
thread
Cable glands
Reference plane for
measuring range
Содержание OPTISOUND 3010 C
Страница 1: ...OPTISOUND 3010 C Handbook Ultrasonic Level Transmitter Four wire 4 20 mA HART...
Страница 49: ...49 Notes OPTISOUND 3010 C Four wire 4 20 mA HART 30504 EN 220310...
Страница 50: ...50 Notes OPTISOUND 3010 C Four wire 4 20 mA HART 30504 EN 220310...
Страница 51: ...51 Notes OPTISOUND 3010 C Four wire 4 20 mA HART 30504 EN 220310...