34
6 Set up with the display and adjustment module
OPTISOUND 3010 C • Four-wire 4 … 20 mA/HART
30504-EN-220310
Simulation
Start simulation?
If the function "
Reset
" is carried out, the sensor resets the values of
the following menu items to the reset values (see table):
4)
Function
Reset value
Max. adjustment
Final value blocking distance in m(d)
5)
Min. adjustment
Meas. range end in m(d)
6)
Medium
Liquid
Vessel shape
not known
Damping
0 s
Linearisation
Linear
Sensor-TAG
Sensor
Displayed value
Distance
Current output - characteristics
4 … 20 mA
Current output - max. current
20.5 mA
Current output - min. current
3.8 mA
Current output - failure
< 3.6 mA
Unit of measurement
m(d)
The values of the following menu items are
not
reset to the reset
values (see table) with " Reset":
Function
Reset value
Backlight
No reset
Language
No reset
HART mode
No reset
Default setting
Like basic adjustment, but in addition, special parameters are reset to
default values.
7)
Peak value indicator
The min. and max. distance and temperature values are reset to the
actual value.
In this menu item you select the internal arithmetic unit of the sensor.
Service - Reset
Service - Adjustment unit
4)
Sensor-specific basic adjustment.
5)
Depending on the sensor type, see chapter "Technical data".
6)
Depending on the sensor type, see chapter "Technical data".
7)
Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.
Содержание OPTISOUND 3010 C
Страница 1: ...OPTISOUND 3010 C Handbook Ultrasonic Level Transmitter Four wire 4 20 mA HART...
Страница 49: ...49 Notes OPTISOUND 3010 C Four wire 4 20 mA HART 30504 EN 220310...
Страница 50: ...50 Notes OPTISOUND 3010 C Four wire 4 20 mA HART 30504 EN 220310...
Страница 51: ...51 Notes OPTISOUND 3010 C Four wire 4 20 mA HART 30504 EN 220310...