Manual OPTISENS AAM 1050
17
OPTISENS AAM 1050
7.2
P / PI controller as impulse-frequency controller
Main menu
.
.
Set points and
controller version
Set points
Set point S1
You can choose different
.
1.50 mg/l
Controller versions
.
P range S1
For S1 and S2
.
0.20 mg/l
Integral time S1
000 sec.
Set point S2
0.50 mg/l
Controller settings
P range S2
Pulse-Freq. S1
0.20 mg/l
0*100/h
Integral time S2
Pulse-Freq. S2
000 sec.
0*100/h
Direction S1
Basic settings
Raise
Basic settings
.
Direction S2
Contr. settings
lower
For an impulse-frequency controller you have to set the following parameters:
1) Set points S1 and S2
S1 refers to relay 1, S2 refers to relay 2.
2) P range and integral action time for S1 and S2
Adjust a P range > 0. For a P controller set integral time = 0, for a PI controller set an integral time > 0.
3) Pulse-frequencies for S1 and S2
Enter the maximum pulse-frequency that corresponds to 100% dosage.
4) The acting direction for S1 and S2
Select „raise“ if the dosage raises the measured value.
Select „lower“ if the dosage lowers the measured value.