background image

14

A Quick Setup

R

Re

eff

D

Diis

sp

plla

ayy

D

De

es

sc

crriip

pttiio

on

n  &

& S

Se

ettttiin

ng

gs

s

A3

Reset

A3.1 Reset Errors

This menu function can be used to reset all
errors that are not removed automatically
(power fail, counter overflow) 
step 1: reset?
N

No

o:

Exit the function 

Y

Ye

es

s

Resets the errors and exits the func-
tion. 

The following reset menus for the counters (totaliser) are only available, if
the quick access has been activated in the menu setup > device > quick
setup. Each counter (totaliser) can be activated for quick access independently. 

A3.2 > FB4 Totaliser 1

(for PROFIBUS Devices) the counter can be
reset to zero in this menu 
step 1: reset counter? 
no: exits the function without reset 
yes: resets the counter and exits the function

A3.3 > FB5 Totaliser 2

for PROFIBUS Devices the counter can be
reset to zero in this menu 
step 1: reset counter? 
N

No

o

exits the function without reset 

Y

Ye

es

s  

resets the counter and exits the func-
tion

A3.4 > FB6 Totaliser 3
(where fitted)

(for PROFIBUS Devices) the counter can be
reset to zero in this menu 
step 1: reset counter?
N

No

o

exits the function without reset 

Y

Ye

es

s

resets the counter and exits the func-
tion 

A4

Station Address

(only for PROFIBUS devices) 
A4 -> Station Address

selects the address of the device at the PROFIBUS

DP interface. 
Note:
The PROFIBUS address can also be changed using the PROFIBUS service
“set_slave_add”. The input range is 0...125 according to the PROFIBUS spec-
ification. Address 126 is the default address and cannot be set via the
PROFIBUS service “set_slave_add” - use menu instead to reset to default
address.

B Test level

B

B3

3

IIn

nffo

orrm

ma

attiio

on

n

B3.5

PROFIBUS

available if there is a PROFIBUS interface in existence; displays the
below mentioned information about the PROFIBUS interface:
KROHNE Ident No.
Software Revision of the PROFIBUS software
Date of Production

2.8 

Display Paramters (PROFIBUS)

(MFC300 PROFIBUS RS-485 Interface with PA Profile 3.01)

For a detailed description please see ”MFC 300 (OPTIMASS) Handbook”. Some special settings concerning
the PROFIBUS features easily operated via the local menu are described in the following tables.

Содержание OPTIMASS MFC 300

Страница 1: ...FC C 3 30 00 0 P PR RO OF FI IB BU US S D DP P R RS S4 48 85 5 d de ev vi ic ce e w wi it th h P PA A p pr ro of fi il le e M MF FC C 3 30 00 0 P PR RO OF FI IB BU US S P PA A M MB BP P d de ev vi ic...

Страница 2: ...2...

Страница 3: ...Structure of Function Block Output Values 12 2 7 Diagnosis 13 2 8 Display Parameters PROFIBUS 14 2 9 Technical Data 21 3 PROFIBUS PA DEVICE MBP INTERFACE PA PROFILE 3 01 3 1 Software History 22 3 2 PR...

Страница 4: ...ym mb bo ol ls s U Us se ed d The follwing is a guide to the meaning of the symbols used in this handbook The symbols fall into two types The rectangular symbols with blue background draws the reader...

Страница 5: ...y Responsibility for suitability and intended use of this device rests solely with the user Improper installation and operation of the device may lead to loss of warranty In addition the Terms and Con...

Страница 6: ...ait approx 10 seconds before you switch off the MFC300 after you have done both a parameter download via PROFIBUS or a manual change of a parameter value via the local display Please wait approx 15 se...

Страница 7: ...thers HW Config others GSD Manufacturer specif ic for standard DP PA segment cou pler KR014510 GSD MFC300 RS 485 Rev 1 GSD Profile specific for standard DP PA seg ment coupler PA039742 GSD Flow dens t...

Страница 8: ...B B D C D C I I I I 5V R2 R1 R1 I 110nH R1 390 R2 220 3 B B D C D C I I I I 5V R2 R1 R1 I 110nH R1 390 R2 220 2 1 External connection PROFIBUS DP device at low datarates connected with spur Spurs are...

Страница 9: ...data exchange of the coriolis mass flow meter MFC300 The application of the manufacturer independent Ident No 9742hex GSD file PA039742 GSD provides interchangeability of devices i e an exchange of co...

Страница 10: ...ings to select the units for local display and PROFIBUS Modifications of the units of the display will have no effect on the data transferred via PROFIBUS A master class 2 tool is required to modify t...

Страница 11: ...6 Slot 6 Index 32 If the value of SetTot changes from 2 to 0 the totaliser starts counting from the current value defined by PresetTot SetTot 2 not allowed Value is ignored totaliser remains in its la...

Страница 12: ...ven in the following tables 2 5 Profiles The MFC300 PROFIBUS RS 485 Interface supports the PROFIBUS PA Profile Version 3 01 The MFC300 PROFIBUS RS 485 Interface with PA Profile 3 01 supports the follo...

Страница 13: ...to get the quality information of the measurement value G Go oo od d n no on n C Ca as sc ca ad de e function block output value is ok and can be used without restrictions G Go oo od d C Ca as sc ca a...

Страница 14: ...ser 3 where fitted for PROFIBUS Devices the counter can be reset to zero in this menu step 1 reset counter N No o exits the function without reset Y Ye es s resets the counter and exits the func tion...

Страница 15: ...l be set in the long status information bytes of the PROFIBUS interface if the actual value of the totaliser is outside these limits This can be also used as a status output choosing the function pres...

Страница 16: ...y voltage for the PROFIBUS C5 y 2 Time Constant Time constant for this function block C5 y 3 Error Behaviour Defines the behaviour of this function block in case of errors Hold Value last valid OUT va...

Страница 17: ...blocks Only PROFIBUS values can be selected here The analogue inputs are shown with exactly the value as seen on the PROFIBUS C6 4 1 Measurement 1 line FB1 Analog inp 1 FB2 Analog inp 2 FB3 Analog inp...

Страница 18: ...6 3 Load Settings in this menu all settings can be loaded from different storage places where settings have been saved before step 1 Load Settings break Exits the menu without loading factory setting...

Страница 19: ...tion Y Ye es s quick access activated N No o quick access not activated C6 9 3 reset totaliser 3 The reset can be activated in the Quick Setup to get a quick access of the function Y Ye es s quick acc...

Страница 20: ...orted no extras D2 2 5 PB Cold Start Reset N No o terminates the function Y Ye es s PROFIBUS cold start will be carried out at once The programming mode is terminat ed N No ot te e During a PROFIBUS c...

Страница 21: ...profile PA Profile compact class B V3 01 Address range 0 126 default 126 0 to 125 via set_slave_add 0 to 126 via Local Display 126 via FACTORY_RESET 2712 Local control local display and operator inter...

Страница 22: ...ibus PA Device V2 2 1 061117 Simatic PCS7 Others HW Config Others GSD Manufacturer specific for standard DP PA segment coupler KR014511 GSD MFC300 MBP Rev 1 GSD Manufacturer specific for segment coupl...

Страница 23: ...In Out 3 Alternative wiring because the current linkage between the device and the PROFIBUS PA cable is not polarised N No ot te e Although the PROFIBUS MBP technology supports power supply via the P...

Страница 24: ...elongs to the KR014511 GSD YP014511 GSD and includes the com plete functionality concerning the cyclic data exchange of the coriolis mass flow meter MFC300 The application of the manufacturer independ...

Страница 25: ...the units for local display and PROFIBUS Modifications of the units of the display will have no effect on the data transferred via PROFIBUS A master class 2 tool is required to modify the units for PR...

Страница 26: ...rer Specific full functionality to Profile Specific interchangeable basic configuration by using a master class 2 tool IDENT_NUM BER_SELECTOR Slot 0 Index 40 change byte value to 0 After this the devi...

Страница 27: ...r coriolis mass flow devices This block provides the parameters and functions defined in PA Profile 3 01 Eight Analog Input AI function blocks as default Mass Flow Density Medium Temperature Volume Fl...

Страница 28: ...to get the quality information of the measurement value G Go oo od d n no on n C Ca as sc ca ad de e function block output value is ok and can be used without restrictions G Go oo od d C Ca as sc ca a...

Страница 29: ...B6 Totaliser 3 for PROFIBUS Devices the counter can be reset to zero in this menu step 1 reset counter N No o exits the function without reset Y Ye es s resets the counter and exits the func tion A4 S...

Страница 30: ...l be set in the long status information bytes of the PROFIBUS interface if the actual value of the totaliser is outside these limits This can be also used as a status output choosing the function pres...

Страница 31: ...y voltage for the PROFIBUS C5 y 2 Time Constant Time constant for this function block C5 y 3 Error Behaviour Defines the behaviour of this function block in case of errors Hold Value last valid OUT va...

Страница 32: ...blocks Only PROFIBUS values can be selected here The analogue inputs are shown with exactly the value as seen on the PROFIBUS C6 4 1 Measurement 1 line FB1 Analog inp 1 FB2 Analog inp 2 FB3 Analog inp...

Страница 33: ...6 3 Load Settings in this menu all settings can be loaded from different storage places where settings have been saved before step 1 Load Settings break Exits the menu without loading factory setting...

Страница 34: ...tion Y Ye es s quick access activated N No o quick access not activated C6 9 3 reset totaliser 3 The reset can be activated in the Quick Setup to get a quick access of the function Y Ye es s quick acc...

Страница 35: ...pported no extras D2 2 5 PB Cold Start Reset N No o terminates the function Y Ye es s PROFIBUS cold start will be carried out at once The programming mode is terminat ed N No ot te e During a PROFIBUS...

Страница 36: ...e_add 0 to 126 via Local Display 126 via FACTORY_RESET 2712 FDE yes separate fault discon nection electronics provided Local control local display and operator interface at device Fault current 6 mA f...

Страница 37: ...37...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...snl net Iran KROHNE Liaison Office North Sohrevardi Ave 26 Sarmad St Apt 9 Tehran 15539 TEL 98 21 874 5973 FAX 98 21 850 1268 e mail krohne krohneiran com Italy KROHNE Italia Srl Via V Monti 75 I 2014...

Отзывы: