Interconnection details:
Terminals marked 6-7-8.
These are used in home automation applications and indicate the unit’s status. There are
two:
o
STATUS OK: No incidents. Contacts 7-6 closed.
o
STATUS NOT OK: Contacts 7-8 closed. Activated whenever there is an incident
affecting the unit, such as lack of salt, lack of flow or excess salt.
There is a delay in activation of this output, i.e. the contacts do not change the moment
the incident is detected to avoid false alarms being sent to any external control
equipment.
Terminals marked 9-10-11.
These are used to control the device and function as follows:
o
TERMINALS 11-9: Responsible for enabling the unit. If the factory-fitted jumper is
removed, the unit will not start. This input is normally used to latch with the filter
pump auxiliary contact or to disable the chlorinator via a home automation system
whenever chlorination is not required.
o
TERMINALS 11-10: This is an input used to force the unit to 100% chlorine
production. When these two terminals are active the unit ignores the input from
the display panel and produces chlorine non-stop.
13. START-UP
To start the unit correctly the steps below must be followed: