Appendix D
RECTIFIER RAM variables
Rectifier RAM variables
Address Bit
no Description
Read/Write
0-1
0
1 = DC ready
Read only
1
1 = Intermediary OK
2
1 = AC input voltage OK
3
1 = Output closed due to high voltage
4
1 = Fan fault
5
1
1 = Alarm, high ambient temperature
6
1 = Alarm, high temperature in cooling body
7
1 = Current limit
8
1 = Output voltage drops below alarm limit for UV alarm
9
1 = Output closed due to low voltage
10 Not
used
11
1 = DC out requested
12
1 = Closed due to “remote off” command via I
2
C
13
1
1 = Closed via “module_disable” in backplane connector
14
1
1 = Closed via “short_pin” in backplane connector (module not sitting properly in place)
15
1
1 = Closed due to timeout in communication with intermediary
2-3
0
1 = Execute lamp test
Write
1
1 = Switch on rectifier
2
1 = Switch off rectifier
3
1
1 = Allow outgoing alarm
4
1
1 = Prevent outgoing alarm
5
1
1 = Fan only run at full speed
6
1
1 = Fan run depending on temperature
7 Not
used
8-15
Rectifier module's I
2
C address
Read only
4-5
Reserved for internal use
6-7
0-15
Output voltage in Volt x 100
Read only
8-9
0-15
Output current in Amperes x 100
Read only
10-11
0-15
Reference value for current limit in Amperes x 100
Read/Write
12-13
0-15
Reference value for output voltage in Volts x 100
Read/Write
14-15
0-15
Reference value for Umaximum (High Voltage Shut Down) in Volts x 100
Read/Write
16-121
Reserved for internal use
122-123
1
0-15
Operating time in hours x 2
Read only
124-125
1
0-15
Alarm limit for under voltage, UV alarm
Read only
126-255
Reserved for internal use
Read only
1) Only relevant for rectifier modules of the type PCV.