7
COMMISSIONING
7.1
SAFETY INSTRUCTIONS
WARNING!
This product contains dangerous voltage that when touched can cause electric shock,
burns or death. All contact safety devices and plates must be fitted when operating.
7.2
ELECTRIFICATION
The equipment becomes live as soon as there is battery voltage to the I/O unit's connection X5:1-
2. After a few seconds, the operator panel display lights up, and after a few more seconds the text
appears on the display. All measurement values are initially reset. The measuring begins after
around 10 seconds. Any alarms are activated when a total of around 30 seconds has passed.
For start-up in general we refer you to the general system manual.
7.3
CHECK OF SETTINGS
Each time the monitoring unit has been without voltage, the built-in clock must be set with the
current date and time, see section
5.5.5.
Check that the measurement values presented agree with the actual position. Check that the
parameters for charging voltages, alarms and other parameters conform to the intended function.
7.4
CHECK OF OUTPUTS
The alarm outputs A-D (A-H if option I/O unit 2 is installed) and the output for fan control can be
operated manually for simple and smooth control of external circuits, see section
5.12.3.