KRACK DLD Series Скачать руководство пользователя страница 4

SLD/DLD/PLD AIR COOLED CONDENSING UNITS 

All equipment should be carefully checked 
for damage as soon as it is received.  If any 
damage is evident, a notation must be made 
on the delivery receipt before it is signed 
and claim should then be filed against the 
freight carrier.  
 
B) CHECK VOLTAGE 
Carefully check nameplate voltage and 
current characteristics to be sure unit is 
compatible with power supply.   
 
C) HANDLING 
Never hoist the unit from any point 
excepting the base lifting holes provided for 
this purpose.  
Lift with spreader and hooks as shown in 
Figure 1.  When moving unit by forklift, lift 
from compressor end ONLY.  Do not lift 
from condenser end. 

 

 
D) LEVELING AND BOLT DOWN 
PROCEDURE 
A solid level foundation should be provided 
for the unit large enough to accommodate 
the full length of the base rails.  If the 
mounting location is not sturdy and perfectly 
level, place shims under low points before 
tightening down with hold-down bolts.  
Improper bolting-down procedure can 
seriously warp the framework, particularly 
with the large condenser fan units (3 fans or 
more). 

 
E) UNIT LOCATION 
Large air-cooled condensing units dissipate 
a tremendous amount of heat and require 
large volumes of air.  Short-circuiting of the 
condenser air, or restricting the free entry of 
air into the coil will result in reduced 
capacity and highpower consumption.  Take 
care to reduce such negative operation 
effects by providing for unrestricted free air 
flow into and from the unit.  At most, the 
unit should not be positioned so as to have 
no more than one of its sides positioned 
close to a vertical building side or wall.  At 
that point, this should be a minimum of 3’ 
unit-to-wall free air clearance distance. 
 
F) LOSS OF GAS HOLDING CHARGE 
Each Condensing unit is evacuated to 
remove moisture, leak tested, and then 
shipped with a gas holding charge. Absence 
of this charge may indicate a leak has 
developed in transit.  The system should not 
be charged with refrigerant until it is 
verified that there is no leak or the source of 
the leak is located. 
 
G) CHECK COMPRESSOR 
The compressor is bolted to the base of the 
condensing unit using solid mounting 
techniques. 
Check the compressor mounting bolts.  
Tighten these bolts as much as possible to 
prevent excess vibration.  Check electrical 
junction connections of the compressor; 
tighten only those that may have come loose 
during transit. 
 

II.   PIPING 
 
1) REFRIGERATION PIPING 

 
Use ACR grade copper tubing, or conform 
otherwise to local and national codes.  
Piping methods must meet these codes and 
result in acceptable piping practice. 
 
A) SUCTION LINE 
Design and sizing of the suction line is 
critical to maintain: 
1) Proper refrigerant velocity 

Содержание DLD Series

Страница 1: ...ATION MANUAL INSTALLING INSTRUCTIONS SLD DLD PLD AIR COOLED CONDENSING UNITS SLD SERIES COND UNITS R 22 R 404A R 507 10 60 HP DLD SERIES COND UNITS R 22 R 404A R 507 7 50 HP CIRCUIT PLD SERIES COND UNITS R 22 R 404A R 507 14 100 HP ...

Страница 2: ...I System Evacuation 5 IV Electrical 5 V Charging the System 5 VI Operation Checkout 5 VII Features and Controls 6 VIII Normal Maintenance 7 TABLES Table 1 Recommended Line Sizes 8 9 Table 2 Condensing Unit Refrigerant Charge 10 11 12 Table 3 Low Pressure Control Settings 13 Table 4 Fan Cycling Control Settings 13 ...

Страница 3: ... 460 3 60 P 575 3 60 Levitor Condenser U 380 3 50 Compressor Manufacture Refrigerant B Bitzer Semi Hermetic 2 R22 C Carlyle Semi Hermetic 4 R404A D Copeland Discus 7 R507 I Ingersoll Rand Semi Hermetic V Copeland Screw Temperature H High Total HP M Medium 0100 10 HP w standard comp L Low 0101 10 HP w oversized comp 0700 2 35 HP w standard comp 0701 2 35 HP w oversized comp Large Condensing Unit Mo...

Страница 4: ...air or restricting the free entry of air into the coil will result in reduced capacity and highpower consumption Take care to reduce such negative operation effects by providing for unrestricted free air flow into and from the unit At most the unit should not be positioned so as to have no more than one of its sides positioned close to a vertical building side or wall At that point this should be ...

Страница 5: ... free rag before fabrication into the system Soft solders should be avoided wherever possible as in most cases they require the use of a flux Most of the low temperature solder flux consists of heavy wax type materials which if allowed to enter the system cause excessive service problems in the form of wax at expansion valves which looks like moisture but cannot be removed by the average dryer cor...

Страница 6: ...e system When initially charging a system that is in a vacuum liquid refrigerant can be directly added into the receiver until the system pressure equalizes with pressure in the refrigerant cylinder Start the system and finish charging until the sight glass is clear Outdoor condensing units are furnished with a condenser flooding type of head pressure control valve for cold weather operation This ...

Страница 7: ...ommended to pump the oil directly into the compressor against suction pressure Refrigerant oil should be purchased in sealed containers and should not be left open to atmosphere Exposure to air and moisture for extended periods will result in contamination of the oil and cause harmful reactions in the compressor Do not transfer oil from one container to another 2 HIGH AND LOW PRESSURE CONTROLS SLD...

Страница 8: ... of the fan rotation 6 CONDENSER FAN CYCLING Pressure switches are included to cycle all but the first condenser fan s in response to head pressure See Table 4 for suggested pressure settings used on all multiple condenser fan systems 7 LOW AMBIENT FLOODING CONTROLS ARE STANDARD Condenser Liquid Flooding utilizes a field adjustable 100 to 225 psig condensate holdback valve Head pressure control va...

Страница 9: ... 1 8 1 2 5 8 5 8 5 8 120 000 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 5 8 5 8 5 8 7 8 150 000 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 2 1 8 2 5 8 5 8 7 8 7 8 7 8 180 000 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 2 5 8 2 5 8 5 8 7 8 7 8 7 8 210 000 1 5 8 2 1 8 2 1 8 2 1 8 2 1 8 2 5 8 2 5 8 2 5 8 5 8 7 8 7 8 7 8 240 000 1 5 8 2 1 8 2 1 8 2 1 8 2 1 8 2 5 8 2 5 8 2 5 8 5 8 7 8 7 8 7 8 300 000 2 1 8 2 1 8...

Страница 10: ...5 8 5 8 5 8 5 8 5 8 84 000 1 1 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 5 8 5 8 5 8 5 8 90 000 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 5 8 5 8 5 8 7 8 120 000 1 3 8 1 5 8 1 5 8 2 1 8 1 5 8 2 1 8 2 1 8 2 1 8 5 8 5 8 7 8 7 8 150 000 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 2 1 8 2 1 8 2 5 8 5 8 7 8 7 8 7 8 180 000 1 5 8 2 1 8 2 1 8 2 1 8 2 1 8 2 1 8 2 5 8 2 5 8 7 8 7 8 7 8 7 8 210 000 1 5 8 2 1 8 2 ...

Страница 11: ... 258 4 SLD 0220 L2 R 22 31 6 47 5 51 8 54 1 55 2 57 1 SLD 0270 L2 R 22 36 9 60 3 66 6 70 0 71 5 74 1 SLD 0300 L2 R 22 36 9 60 3 66 6 70 0 71 5 74 1 SLD 151 L2 R 22 36 9 60 3 66 6 70 0 71 5 74 1 SLD 0221 L2 R 22 36 9 60 3 66 6 70 0 71 5 74 1 SLD 0271 L2 R 22 36 8 53 8 62 1 54 9 68 4 71 4 SLD 0301 L2 R 22 50 2 75 6 87 9 77 0 97 3 101 6 SLD 0150 M4 R 404A 27 9 33 4 40 2 44 2 45 7 48 1 SLD 0200 M4 R 4...

Страница 12: ...0 6 67 1 69 5 73 4 DLD 0601 H2 R 22 55 7 63 9 82 7 92 4 95 9 101 7 DLD 0701 H2 R 22 80 4 91 5 116 6 129 7 134 5 142 2 DLD 0801 H2 R 22 90 8 95 9 126 1 145 9 152 3 164 1 DLD 1001 H2 R 22 117 9 122 3 147 4 176 9 1067 7 203 1 DLD 1201 H2 R 22 136 6 141 6 157 9 198 1 209 5 231 5 DLD 0440 L2 R 22 23 9 36 5 42 7 37 2 47 3 49 4 DLD 0540 L2 R 22 27 8 44 5 52 6 45 3 58 7 61 5 DLD 0600 L2 R 22 36 9 60 3 66 ...

Страница 13: ...71 1 91 3 95 5 PLD 0540 L2 R 22 52 6 85 9 102 1 87 3 114 2 119 7 PLD 0600 L2 R 22 58 3 104 5 116 8 123 3 126 2 131 2 PLD 0441 L2 R 22 52 6 85 9 102 1 87 3 114 2 119 7 PLD 0541 L2 R 22 63 4 124 5 140 6 149 1 152 8 159 1 PLD 0601 L2 R 22 73 9 123 6 147 9 125 6 165 9 174 1 PLD 0500 M4 R 404A 70 8 75 7 91 9 106 8 112 5 121 0 PLD 0600 M4 R 404A 95 1 116 1 143 2 158 8 164 6 173 7 PLD 0700 M4 R 404A 85 7...

Страница 14: ...ture at the condensing unit or the box design temperature whichever is lower Example 1 30 F minimum ambient 20 F freezer Use 20 F value from Table Example 2 10 F minimum ambient 35 F cooler Use 10 F value from Table TABLE 3B HIGH PRESSURE CONTROL SETTINGS R 22 400 Psig R 404A R 507 400 Psig TABLE 4 FAN CYCLING CONTROL SETTINGS Number of Fans Control Cut In Settings PSIG Single Row Double Row Refri...

Отзывы: