SLD/DLD/PLD AIR COOLED CONDENSING UNITS
13
TABLE 3A
LOW PRESSURE CONTROL SETTINGS
M
Temperature
R-22
Max Cut In Cut Out
R-404A
Max Cut In Cut Out
50 F
70 Psig
30 Psig
85 Psig
40 Psig
40 F
55 Psig
25 Psig
70 Psig
35 Psig
30 F
40 Psig
20 Psig
50 Psig
30 Psig
20 F
30 Psig
10 Psig
40 Psig
20 Psig
10 F
20 Psig
5 Psig
30 Psig
10 Psig
0 F
15 Psig
0 Psig
25 Psig
5 Psig
-10 F
10 Psig
0 Psig
15 Psig
0 Psig
-20 F
8 Psig
0 Psig
10 Psig
0 Psig
+ Temperature is the minimum ambient temperature at the condensing unit or the box design temperature,
whichever is lower.
Example #1: 30 F minimum ambient, -20 F freezer. Use -20 F value from Table.
Example #2: -10 F minimum ambient, +35 F cooler. Use -10 F value from Table.
TABLE 3B
HIGH PRESSURE CONTROL SETTINGS
R-22
400 Psig
R-404A/R-507
400 Psig
TABLE 4
FAN CYCLING CONTROL SETTINGS
Number of Fans
Control Cut In Settings-PSIG
Single Row
Double Row
Refrigerant FCP-1
FCP-2
FCP-3
FCP-4
2
4
R-22
215
R-404A
220
3
6
R-22
215
230
R-404A
220
245
4
8
R-22
215
230
245
R-404A
220
245
265
5
10
R-22
215
225
235
245
R-404A
220
235
250
265
Note: Settings based on 20 TD. Set cut out 35 psig below cut in. Fan(s) on header end to remain on at all times.