background image

#SP-34 LE & MV R.5 January 2020

Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces

INTRODUCTION  7

1.0  INTRODUCTION

1.1  Appliance Certification

Laboratory: PFS in Cottage Grove, Wisconsin 
Standards: 
ANSI Z21.88-2017/CSA 2.33-2017, Vented Gas Fireplace Heaters
CSA 2.17 2017, Gas-Fired Appliances for Use at High Altitudes

This installation must conform with local codes, or in the absence of 

local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or 

the Natural Gas and Propane Installation Code, CSA B149.1.

1.2  California Proposition 65 Warning

WARNING: This product can expose you to chemicals including 

Carbon Monoxide, that is an externally vented by-product of fuel 

combustion, which is [are] known to the State of California to cause 

birth defects or other reproductive harm. For more information, visit 

www.P65Warnings.ca.gov.

1.3  Requirements for the 

Commonwealth of Massachusetts

The following requirements reference various Massachusetts and 

national codes not contained in this manual.

For all sidewall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part for 

residential purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent termination 

is less than (7) feet above finished grade in the area of the venting, 

including but not limited to decks and porches, the following 

requirements shall be satisfied:

1.3.1  Installation of Carbon Monoxide Detectors

At time of installation of side wall horizontally vented gas fueled 

equipment, the installing plumber or gas-fitter shall observe that 

a hard wired carbon monoxide detector with an alarm and battery 

back-up is installed on the floor level where the gas equipment is 

to be installed. In addition, the installing plumber or gas-fitter shall 

observe that a battery operated or hard wired carbon monoxide 

detector is installed on each additional level of the dwelling, building 

or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner 

to secure the services of qualified licensed professionals for the 

installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or attic, the hard wired carbon 

monoxide detector with alarm and battery back-up may be installed 

on the next adjacent floor level. In the event that the requirements 

of this subdivision can not be met at the time of completion of 

installation, the owner shall have a period of thirty (30) days to 

comply with the above requirements; provided, however, that during 

said thirty (30) day period, a battery operated carbon monoxide 

detector with an alarm shall be installed.

1.3.2  Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the 

above provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

1.3.3  Signage

A metal or plastic identification plate shall be permanently mounted 

to the exterior of the building at a minimum of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the 

horizontally vented gas fueled heating appliance or equipment. The 

sign shall read, in print no less the one-half inch (½) in size, “GAS VENT 

DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”. 

1.3.4  Inspection

The state or local gas inspector of the side wall horizontally vented 

gas fueled equipment shall not approve the installation unless, upon 

inspection, the inspector observes carbon monoxide detectors and 

signage installed in accordance with the provisions of 248 CMR 5.08 

(2) (a) 1 through 4.

1.3.5  Exemptions

The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 

through 4: The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition of NFPA 54 as 

adopted by the Board; and Product Approved side wall horizontally 

vented gas fueled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or in part for 

residential purposes.

1.3.6  Manufacturer Requirements

1.3.6.1  Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally 

vented gas equipment provides a venting system design or venting 

system components with the equipment, the instructions provided 

by the manufacturer for installation of the equipment and the 

venting system shall include:
• 

Detailed instructions for the installation of the venting system 

design or the venting system components; and

• 

A complete parts list for the venting system design or venting 

system.

1.3.7  Gas Equipment Venting 

System NOT Provided

When the manufacturer of Product Approved side wall horizontally 

vented gas equipment does not provide the parts for venting the 

flue gases, but identifies “special venting systems”, the following 

requirements shall be satisfied by the manufacturer:
• 

The referenced “special venting systems” instructions shall 

be included with the appliance or equipment installation 

instructions and;

• 

The “special venting systems” shall be Product Approved by the 

Board, and the instructions for that system shall include a parts 

list and detailed installation instructions.

A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all venting 

design instructions shall remain with the appliance or equipment at 

the completion of the installation.

Содержание SP-34-LE

Страница 1: ...or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless...

Страница 2: ......

Страница 3: ...________________________________________________________________ ____________________________________________________________________________________________________________________ CON GRAT ULAT ION...

Страница 4: ......

Страница 5: ...1 Vertical Vent Cap Termination 22 6 2 Minimum Termination Clearances 23 7 0 VENTING 24 7 1 Approved Vent Systems 24 7 2 Venting Requirements 24 7 3 Use of Elbows 24 7 4 Restrictor Plate Assembly and...

Страница 6: ......

Страница 7: ...eriod a battery operated carbon monoxide detector with an alarm shall be installed 1 3 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above provi...

Страница 8: ...ocal authorities or codes having jurisdiction in your area regarding derate guidelines 2 1 1 1 US Installations Refer to the American Gas Association guidelines for the gas designed appliances deratin...

Страница 9: ...y Heat Fireplaces SPECIFICATIONS 9 2 3 Appliance Dimensions Figure 2 1 Appliance Dimensions 51 8 131mm 307 8 786mm 13 342mm 28 711mm 34 864mm 7 198mm 20 519mm 333 8 848mm 14 356mm TOP VIEW LEFT SIDE F...

Страница 10: ...viduals If the barrier becomes damaged the barrier shall be replaced with Hussong Mfg s barriers for this appliance IMPORTANT Consider the height of hearth finish material when building a fireplace pl...

Страница 11: ...wo studs eliminating the need for any additional framing Please be aware of the large amount of heat this fireplace will produce when determining a location 3 2 Floor Support and Protection Floor prot...

Страница 12: ...E Thenailingtabsonbothsidesoftheapplianceallowinstallations for a flush mount 1 2 13mm facing material or 5 8 16mm facing material CAUTION Never permanently remove these assemblies from the fireplace...

Страница 13: ...to fireplace enclosure top 12 305mm Appliance sides to adjacent sidewall 4 1 2 114mm Fireplace enclosure floor to 3 4 19mm trim 33 1 2 108mm Mantel 6 152mm deep from fireplace enclosure floor 37 940m...

Страница 14: ...to support the added weight of the masonry construction above the fireplace If installing optional fan assembly SP 028 it is easier to install before unit installation Please refer to Section 9 3 SP 0...

Страница 15: ...e maintained 1 Measure from floor level of the fireplace to the center of where the vent pipe will penetrate the wall Elbows listed with approved vent systems for this appliance vary in vertical lengt...

Страница 16: ...ation A outdoor covered fireplace installation allows a fireplace to be installed in an outdoor covered area where the appliance is protected from direct precipitation Follow the instructions and illu...

Страница 17: ...tion Minimum weatherproof overhang in front and sides M i n i m u m w e a t h e r p r o o f o v e r h a n g i n f r o n t a n d s i d e s Minimum weatherproof overhang in front and sides M i n i m u m...

Страница 18: ...2mm above the appliance to a maximum 6 152mm depth of a non combustible mantel Follow projection 1 25mm up for every 1 25mm deeper 4 1 2 Adjacent Sidewall Requirements The adjacent sidewall must be 4...

Страница 19: ...CING AND FINISHING 19 Figure 4 1 Clearances to Combustibles 14 356mm 35 895mm 42 1067mm 37 940mm 33 851mm 19mm 6 152mm 1 25mm 4 108mm 12 305mm TRIM 12mm COMBUSTIBLE FACING MATERIAL ALLOWED 14 356mm 42...

Страница 20: ...screen lift the screen up and out of slots 4 2 2 Overlay Designs SP34 POL SP34A POL 1 If installed remove the safety barrier screen 2 Center the overlay over the safety screen 3 Locate the 4 tabs on...

Страница 21: ...re Requirements SP 34 LE Electronic Gas Pressure Natural Gas Propane Minimum Inlet Pressure 5 WC 1 25 kPa 7 WC 1 74 kPa recommended 12 WC 2 99 kPa recommended Maximum Inlet Pressure 10 5 WC 2 62 kPa 1...

Страница 22: ...0 30 Over 6 12 to 7 12 1 25 0 38 Over 7 12 to 8 12 1 5 0 46 Over 8 12 to 9 12 2 0 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1 22 Over 12 12 to 14 12 5 0 1...

Страница 23: ...building or the combustion air inlet to any other appliance 12 30cm 9 23cm K Clearance to mechanical air supply inlet 6 1 83m 3 91cm above if within 10 3m horizontally Massachusetts 10 3m L Clearance...

Страница 24: ...g unfaced insulation products listed as noncombustible per ASTM E 136 Flame height and appearance will vary depending upon venting configuration and the type of fuel used Refer to the vent manufacture...

Страница 25: ...rtical vent heat shield must be installed for every vent configuration See Section 7 9 on page 32 i Minimum Maximum Vertical Venting 3 914mm minimum vertical length 50 15 24m maximum vertical length t...

Страница 26: ...Vertical Rise Minimum Horizontal Run Maximum Horizontal Run 9 228mm minimum vertical rise 90 horizontal elbow 6 152mm minimum horizontal run 10 3m maximum horizontal run termination cap See Figure 7...

Страница 27: ...ical and maximum horizontal combination venting the vent terminations must be within the shaded area in Figure 7 2 The vertical vent heat shield must be installed for every vent configuration See Sect...

Страница 28: ...7 8 Metalbestos 8 American Metals 6 Jackes Evans 7 8 Jackes Evans 8 Air Jet 6 Hart Cooley 7 8 Hart Cooley 8 Metal Fab 6 Pro Jet 7 8 Pro Jet 6 7 American Metals 6 7 Metal Fab 6 Air jet 7 6 1 4 Flex Pi...

Страница 29: ...eld assembly must be installed when incorporatingminimumhorizontalventingoffthetopoftheappliance IMPORTANT Careshouldbetakenwheninstallingflexiblepipetoavoid a tight bend that may cause abrasion or da...

Страница 30: ...nsulation products listed as non combustible per ASTM E 136 3 Apply a liberal bead of exterior sealant around outer edge of termination box A Place assembly through the wall pass through in exterior w...

Страница 31: ...he 1 25mm top required clearance Hand bend the 6 tabs on the sides and bottom of the wall pass through Repeat for the other section 2 From the interior install one section of the wall pass through Sec...

Страница 32: ...installation 2 Align the 2 slots on the vertical heat shield flanges with corresponding screw holes located in front of the flue outlet on the top of the fireplace 3 Secure the vertical vent heat shie...

Страница 33: ...ss panel 1 Locate 2 spring loaded latches securing the glass assembly at the bottom of the firebox 2 Pull the spring loaded latches out and down to release the bottom of the glass assembly 3 Life glas...

Страница 34: ...log SP34 1A on the back log plate 2 Align the holes in log SP34 2A with the mounting pins on the left front log plate Push log down to seat 3 Align the holes in log SP34 3A with the mounting pins on t...

Страница 35: ...ebox floor 13 Lift the control board out of the firebox being careful not to damage the sealing gasket underneath 8 3 2 Control Board Installation 1 Place control board in the firebox aligning the hol...

Страница 36: ...operational control using low voltage wires not included It is optional to disable the main ON OFF rocker switch operating the main burner by disconnecting the wires from the control module Figure 9 1...

Страница 37: ...Switch PILOT BURNER PILOT IGNITER FLAME SENSOR APPLIANCE GROUND STAR MALE END BATTERY PACK IPI CPI SWITCH MAIN ON OFF SWITCH 886 PROFLAME PILOT BURNER PILOT IGNITER FLAME SENSOR APPLIANCE GROUND STAR...

Страница 38: ...ERMOCOUPLE THERMOPILE PILOT PIEZO WIRE ASSEMBLY not included Attach gas valve connectors to the wall switch thermostat wires connect to top and bottom terminals marked TH and TP TH on gas valve Figure...

Страница 39: ...kit includes 1 Fan assembly 2 Philips head screws black 1 Temperature control switch with magnet attached 1 Speed control box with cord 1 Before unit installation remove the back access panel 4 screw...

Страница 40: ...r switch Press the ON OFF rocker switch to OFF 5 Locate the manual valve installed by your qualified service technician 6 Turn the manual valve clockwise to the OFF position 7 Wait five 5 minutes to c...

Страница 41: ...for 7 consecutive days once the pilot has been ignited If you have your Proflame 2 system set to CPI continuous pilot ignition with 7 consecutive days without ignition of the main burner the pilot wi...

Страница 42: ...ion above on this page 2 Set thermostat to lowest setting if applicable 3 Turn off all electric power to the appliance 4 Open the control compartment access panel 5 Push in gas control knob slightly a...

Страница 43: ...model SP 34 MV is fitted with a millivolt Pilot on Demand gas control valve equipped with a timer set for 7 consecutive days once the pilot has been ignited If there is no appliance operation within...

Страница 44: ...pressure settings 6 Set IPI CPI rocker switch to IPI OFF Press the main ON OFF rocker switch to OFF Pilot and burner should turn off 7 Disconnect hose and tighten the inlet IN pressure tap by turning...

Страница 45: ...switch to OFF 7 Turn the gas control knob to OFF 8 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not over tighten 9 Relight pilot and turn t...

Страница 46: ...tioning before adjusting the venturi Logs must not block burner ports 1 Open control compartment access panel 1 Remove the safety barrier and glass frame assembly 2 Remove the log set and lava rock 3...

Страница 47: ...t the baffle out of slots on the firebox back wall 4 Bend the tabs on the restrictor plate included in fireplace components packet to approximately 80 angles This will create tension when the restrict...

Страница 48: ...tween the appliance and main gas line Pilot will not stay lit No propane in tank Check propane tank Refill if necessary Low gas pressure Consult a plumber or a gas supplier Can be caused by situations...

Страница 49: ...t restriction after installation on page 47 Soot appears on glass Improper log placement Refer to Section 8 2 SP34 50A Log Set Installation on page 34 Improper venturi setting Venturi air shutter may...

Страница 50: ...connection at gas valve is full inserted and tight hand tight plus 1 4 turn Thermocouple reading below 15 millivolts Disconnect the thermocouple from valve Place one millivolt meter lead wire on the...

Страница 51: ...nd burner extinguish while in operation No propane in tank Check propane tank Refill if necessary Incorrect glass frame assembly installation Refer to Section 8 1 Glass Frame Assembly on page 54 Impro...

Страница 52: ...on Refer to Section 7 0 Venting on page 24 Performed by Qualified Service Person Frequency Annually Action Examination of the vent system is required The flow of combustion and ventilation air must no...

Страница 53: ...ice Visually check pilot light when in operation Continuous Pilot Ignition System Millivolt Ensure pilot flame impinges on thermocouple Clean pilot hold and adjust pilot flame at gas valve for proper...

Страница 54: ...c P O Box 577 204 Industrial Park Drive Lakefield MN 56150 0577 USA SP 34 MV and SP 34 LE SP 34 LE CONTROL BOARD AND PARTS Control Board Natural Gas SP34 140A Pilot Assembly Propane 700 551 1 Control...

Страница 55: ...SP34 4A Log SP34 4A SP34 5A Log SP34 5A SP34 6A Log SP34 6A 1 2 Lava Rock 600 702 Rock Wool Embers 900 REMB GLASS AND GLASS GASKET 28 x 20 1 2 Glass with Gasket 701 016T 1 1 8 Glass Gasket 900 006 Val...

Страница 56: ......

Страница 57: ...of but not limited to improper chimney venting installation will also render this warranty void 7 This warranty does not cover installation and operational related problems such as environmental cond...

Страница 58: ......

Отзывы: