  TERMINATION LOCATIONS

5.0  TERMINATION LOCATIONS

5.1  Vertical Vent Cap Termination

WARNING: This gas appliance must not be connected to a 
chimney serving any other appliance.

Minimum height (H) from roof

Roof Pitch

Feet

Meters

Flat to 6/12

1.0

0.30

Over 6/12 to 7/12

1.25

0.38

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2.0

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4.0

1.22

Over 12/12 to 14/12

5.0

1.52

Over 14/12 to 16/12

6.0

1.83

Over 16/12 to 18/12

7.0

2.13

Over 18/12 to 20/12

7.5

2.27

Over 20/12 to 21/12

8.0

2.44

12

x

ROOF PITCH = x/12

H

H

LOWEST 

DISCHARGE 

OPENING

APPROVED CAP

APPROVED 

VENT PIPE

H - MINIMUM HEIGHT FROM ROOF TO 
LOWEST DISCHARGE OPENING

MINIMUM

*12” (.30 m)

*If vent is closer than 12 in (.30 m), it must terminate at least 2 
ft (.61 m) higher than any portion of a building within 10 ft (3.05 
m) of the vent. 

Figure 5.1, Vertical Vent Cap Clearance

Содержание BIRCHWOOD-20 LOG

Страница 1: ...where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit...

Страница 2: ......

Страница 3: ...r safety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong President Dudley Hussong Board Chairman Homeown...

Страница 4: ......

Страница 5: ...al Terminations 20 6 6 Combination Venting 21 7 0 FIREPLACE SET UP 22 7 1 Safety Barrier Installation 22 7 2 Glass Frame Assembly 22 7 3 BW20 500 Log Set Installation 23 7 4 Control Board Removal and...

Страница 6: ......

Страница 7: ...he above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 1 2 3 Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the bu...

Страница 8: ...e Low 1 1 WC 0 27 kPa 2 9 WC 72 kPa Orifice Size DMS FRONT 0625 BACK 44 FRONT 61 BACK 54 2 2 1 Altitude Adjustment This appliance may be installed at higher altitudes Please refer to National Fuel Gas...

Страница 9: ...mensions 2313 16 605mm 615 16 176mm 201 16 510mm 141 8 359mm 2515 16 658mm 30 781mm 7 185mm 15 400mm 1713 16 452mm 7 185mm 27 658mm LEFT SIDE FRONT VIEW RIGHT SIDE TOP VIEW Figure 2 1 Appliance Dimens...

Страница 10: ...mm 201 16 510mm 141 8 359mm 7 185mm 3515 16 913mm 13 349mm 17 451mm 181 8 461mm 27 704mm 121 8 308mm 1713 16 452mm 7 185mm 27 658mm TOP VIEW LEFT SIDE FRONT VIEW RIGHT SIDE Figure 2 2 Appliance Dimens...

Страница 11: ...1713 16 452mm 7 185mm 27 658mm 201 16 510mm 7 184mm 2313 16 605mm 85 8 219mm 121 8 308mm 141 8 359mm 155 16 389mm TOP VIEW LEFT SIDE FRONT VIEW RIGHT SIDE Figure 2 3 Appliance Dimensions shown with c...

Страница 12: ...ion of children and other at risk individuals If the barrier becomes damaged the barrier shall be replaced with Hussong Mfg s barriers for this appliance Only doors certified with the appliance shall...

Страница 13: ...s eliminating the need for any additional framing This fireplace may be installed in a bedroom Please be aware of the large amount of heat this fireplace will produce when determining a location 1 25m...

Страница 14: ...ulated to prevent cold air from entering room Follow vent pipe manufacturer s installation instructions for vertical terminations A minimum of 1 in 25 mm clearance on all sides of the vertical vent pi...

Страница 15: ...system at pressures in excess of psi 3 5 kPa For test pressures equal to or less than psi 3 5 kPa the appliance must be isolated from the gas supply piping system by closing its individual manual shu...

Страница 16: ...2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1 22 Over 12 12 to 14 12 5 0 1 52 Over 14 12 to 16 12 6 0 1 83 Over 16 12 to 18 12 7 0 2 13 Over 18 12 to 20 12 7 5 2 27 Over 20 12 to 2...

Страница 17: ...combustion air inlet to any other appliance 12 in 30 cm 9 in 23 cm K Clearance to mechanical air supply inlet 6 ft 1 83 m 3 ft 91 cm above if within 10 ft 3 m horizontally Massachusetts 10 ft 3 m L Cl...

Страница 18: ...acturer s installation manual for complete installation instructions Vent installation must conform with venting requirements and restrictions as outlined in this manual Provide a means for visually c...

Страница 19: ...appearance 6 4 1 Restrictor Plate Assembly and Installation A restrictor plate included in components packet may be installed before vent installation to achieve desired flame appearance Hussong Manuf...

Страница 20: ...l Length 3 ft 914 mm 50 ft 15 2 m Table 6 4 Recommended Restriction for Vertical Terminations Gas Type Vent Configuration Baffle Position Restrictor NG Minimum vertical Setting 5 Install restrictor Re...

Страница 21: ...in 1219 mm Table 6 6 NG LPG Max Vertical Max Horizontal Combination Maximum Vertical Rise Maximum Horizontal Run Total Length 25 ft 7 6 m 25 ft 7 6 m 50 ft 15 2 m Maximum number of 90 elbows 5 Table 6...

Страница 22: ...ly should be done by a licensed or qualified service person 7 2 1 Remove Glass Frame Assembly WARNING Do not remove the glass assembly when hot 1 Remove the safety screen 2 Locate 2 spring loaded latc...

Страница 23: ...nstructions and illustrations for proper log placement 1 Align the holes in the bottom of the ember panel with the 2 mounting pins located on left and right side of the front burner Push to seat 2 Ali...

Страница 24: ...8 Remove the front burner from the firebox 4 screws 9 Remove and save 10 screws securing the control board Lift the control board and control module out of the firebox being careful not to damage seal...

Страница 25: ...r remove the grounding prong from this plug 8 1 Electrical Specifications This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes wi...

Страница 26: ...ed in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 This kit includes 1 Fan assembly mounted 4 F...

Страница 27: ...e appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier OPERATING INSTRUCTIONS NOTE When this fireplace is initially lit cond...

Страница 28: ...position for remote control operation of the main burner and fireplace features 9 3 Reset the System for Manual Operation 1 Set the ON OFF rocker switch to OFF position 2 Press the red SWI button on t...

Страница 29: ...imately 2 seconds move the switch to the ON position The ignition sequence will start again 9 6 1 2 Remote Control ON OFF Key 1 Press the remote control ON OFF key to turn the system OFF 2 After appro...

Страница 30: ...t option The standing pilot will keep the firebox warm and establish a draft in the vent which allows the main burner to ignite with less air flow disruption When the system is OFF the LCD screen will...

Страница 31: ...e set to a desired temperature to control a room s comfort level To activate this function 1 Press the thermostat key The LCD screen will display a temperature bulb graphic the room temperature and se...

Страница 32: ...ode Fan s will operate at previous setting There is no delay in start up or stop time 9 8 9 Accent Light Kit if applicable The light intensity can be adjusted through 6 levels 1 Press the mode key to...

Страница 33: ...ximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not over tighten 6 Relight pi...

Страница 34: ...may lift off the burner 10 2 1 1 Venturi Opening Adjustment NOTE If soot is present on the glass check log positioning before adjusting the venturi Logs must not block burner ports IMPORTANT Slight ad...

Страница 35: ...ommendations for venting installations please refer to Table 6 4 Recommended Restriction for Vertical Terminations on page 20 and Table 6 7 Recommended Restriction for Combination Venting on page 21 T...

Страница 36: ...of the baffle above flange along the inside top of firebox opening Tip the baffle against the firebox back wall and secure with 4 screws previously removed 6 Reinstall all components previously remov...

Страница 37: ...gas in tank Check LP propane tank Refill if necessary Low gas pressure Consult a plumber or a gas supplier Can be caused by situations such as a bent line too narrow diameter or pipe or a low line pr...

Страница 38: ...ir into the gas mix Refer to Section 12 2 1 1 Venturi Opening Adjustment on page 39 Incorrect vent cap installation Adjust if necessary Vent cap blockage Remove debris if necessary Improper pitch on h...

Страница 39: ...aled and require no oiling 12 3 Vent System NOTE If the vent air intake system is disassembled for any reason reinstall per instructions provided with installation Refer to Section 6 0 Venting on page...

Страница 40: ...nversion Kit NG NCK BW20L S 540 Split Flow 700 595 Conversion Kit LPG LCK BW20L S Transmitter Remote Control 700 408 Front Burner BW20 350 Pilot Orifice NG 62 700 166 Back Burner BW20 351 Pilot Orific...

Страница 41: ...ng Manufacturing Co Inc s behalf any additional obligation of liability connected with the unit It is expressly agreed and understood that this warranty is Hussong Manufacturing Co Inc s sole obligati...

Страница 42: ......

Страница 43: ...efective component s It is expressly agreed and understood that this Lifetime Warranty is Hussong Manufacturing Co Inc s sole obligation and original purchaser s exclusive remedy for defective firepla...

Отзывы: