If the air conditioner is mounted to the cabinet door you must be sure that the door hinges
will support the additional weight of the air conditioner. Also be certain that when the door
is opened fully, the cabinet does not become unbalanced. The actual weight of the unit can
be found in the performance specifications on page 11.
CAUTION
Drawings and Dimensions
(9) .312 [7.9]
DIA. HOLES
1.25
[31.7]
10.00
[254.0]
1
2
5.85
[148.6]
.50
[12.7]
7.88
[200.1]
9.75
[247.6]
7.88
[200.1]
1.29
[32.7]
TYP.
.85
[21.6]
9.50
[241.3]
TYP.
1.61
[40.9]
8.50
[215.9]
12.69
[322.3]
3.30
[83.8]
8.50
[215.9]
MOUNTING PLAN
Dimensions, inches [mm], are for reference only and are subject to change.
WARM AIR RETURN FROM
ENCLOSURE
COOL AIR OUTLET
TO ENCLOSURE
1
2
Mounting (con’t)
1.
These externally mounted air conditioners have pre-installed
gaskets to ensure a proper seal. This seal is necessary to
maintain the integrity of the closed-loop system and the
enclosure NEMA 4 or NEMA 4X Rating.
2.
Attach mounting hooks to unit using the supplied (4) #10 -32 x
1/
2
screws, two per hook.
3.
Position the air conditioner against the enclosure with the
mounting hooks in the upper cutout to aid in aligning the
mounting holes.
4.
Secure the air conditioner to the enclosure using the supplied
(9)
1/
4
-20 x 1-
inch bolts and washers.
5.
Attach plastic drain hose to the drain tubing on the bottom of the
air conditioner with a clamp.
HOOK
HOOK
K3NA4C4SP28L