Principles of Operation (con’t)

MAX AND MIN TEMPERATURE MEMORIZATION

HOW TO SEE THE MIN TEMPERATURE:

1) Press and release the down arrow       key.

2) The “Lo” message will be displayed followed 

by the minimum temperature recorded.

3) Press the down arrow       key again or wait 5 seconds

to restore normal display.

HOW TO SEE THE MAX TEMPERATURE:

1) Press and release the up       arrow key.

2) The “Hi” message will be displayed followed 

by the maximum temperature recorded.

3) Press the up arrow        key again or wait 5 seconds to

restore normal display.

HOW TO RESET THE MAX AND MIN TEMPERATURE
RECORDED:

1) Press the SET key for more than 3 seconds while the

max or min temperature is displayed. (rSt message 
will be displayed.)

2) To confirm the operation, the “rSt” message starts 

blinking and the normal temperature will be displayed.

MAIN FUNCTIONS

HOW TO SEE THE SETPOINT:

1) Press and immediately release the SET key. 

The display will show the set point value.

2) Press and immediately release the SET key, or 

wait 5 seconds to display the probe value again.

HOW TO CHANGE THE SETPOINT:

NOTE: The standard set point is 75°. 

1) Press the SET key for more than 2 seconds to 

change the set point value.

2) The value of the set point will be displayed and 

the °

or °

LED starts blinking.

3) To change the set value push the up        or down 

arrow        keys within 10 seconds.

4) To store the new set point value push the SET 

key again, or wait 10 seconds. 

HOW TO CHANGE A PARAMETER VALUE:

To change a parameter’s value, operate as follows:

1) Enter the Programming mode by pressing the  

SET plus down arrow keys for 3 seconds (the 
°

or °

LED starts blinking).

6

2) Select the required parameter. Press the SET 

key to display its value. 

3) Use up or down arrow keys to change its value.

4) Press SET to store the new value and move to

the following parameter. To exit, press SET and
the up arrow keys or wait 15 seconds without 
pressing a key.

NOTE: The set value is stored even when the 
procedure is exited by waiting for the time-out 
to expire.

HOW TO LOCK THE KEYBOARD:

1) Press and hold the up and down arrow keys 

simultaneously for more than 3 seconds. 

2) The POF message will be displayed, and the 

keyboard will be locked. At this point, it will only
be possible to see the set point or the MAX or 
MIN temperature stored. 

3) If a key is pressed more than 3 seconds, the 

POF message will be displayed.

HOW TO UNLOCK THE KEYBOARD:

1) Press and hold the up and down arrow keys 

simultaneously for more than 3 seconds until 
the Pon message is displayed. 

OPTIONAL MONITORING SYSTEM

TTL SERIAL LINE - FOR OPTIONAL MONITORING
SYSTEMS:

The optional TTL serial line, available through the
HOT KEY connector, allows through the use of
the external TTL/RS485 converter, connection of
this digital converter to a monitoring system that is
ModBUS-RTU compatible (X-WEB500/3000/300).
Connections are provided through an external 2-
position terminal block.

Содержание Slimkool K3NA4C4SP28L

Страница 1: ...IS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 81 1 19 CDR 20131 SLIMKOOL SERIES K3...

Страница 2: ...c model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtual...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...H Cooling BTU H Max Ambient Temperature Min P S I G P S I G Design Pressure Low Side Design Pressure High Side Oz Factory Charge Refrigerant Max Fuse Size HACR Type Circuit Breaker Min Circuit Ampacit...

Страница 5: ...n discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperature...

Страница 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...trical power on 4 Verify that the evaporator blower or fan is running 5 Observe the temperature on the digital display The thermostat must be set a minimum of 10 F below this temperature for the compr...

Страница 9: ...m are for reference only and are subject to change WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 1 2 Mounting con t 1 These externally mounted air conditioners have pre installed gaskets...

Страница 10: ...3 TYP 27 94 709 6 66 16 8 4 00 101 6 TYP 13 54 343 9 TYP 11 79 299 4 2 75 70 0 TYP 3 96 100 5 1 11 28 1 3 07 78 0 2 64 67 0 10 37 263 3 1 59 40 3 8 76 222 5 DRAIN TUBE 5 83 148 0 1 48 37 5 1 2 2 3 4...

Страница 11: ...36 01 Transformer 0932 38 Fuses 2 0916 30 Phase Protector 0694 73 Overload 0694 72 Overload base 0694 74 Filter 9501F SLIMKOOL NEMA 4X model offered with these additional features Stainless Steel Shel...

Страница 12: ...or threshold setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and conden...

Страница 13: ...lity They are designed to require only routine maintenance If your air conditioner should require warranty service please contact Kooltronic If you require service out of warranty we have compiled a t...

Страница 14: ...difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Evaporator Coil...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: