VII. Specific Model Data

Mounting

The Kooltronic Special Purpose Air Conditioners K3NA4C4SP28L have been engineered to be installed easily. Prior
to mounting, refer to page 9 and 10 for the mounting plan and the general arrangement drawings showing
dimensions and locations of mounting holes and cutouts. Prior to cutting or drilling, make sure that cutouts and
mounting holes do not interfere with components inside the cabinet. To avoid damaging your air conditioner, please
read the following information before installation:

V. Principles of Operation (con’t)

This unit is equipped with a Temperature Alarm, which has normally closed and normally open contacts, and a factory
set point of 115°F.

The optional heater consists of a heater, a control thermostat and a limiter. The control thermostat is a bimetal disk
with a fixed set point of 60°F. When the entering evaporator air temperature rises above 60°F the heater shuts off,
and when the evaporator air temperature falls below 40°F the heater will engage. The limiter features a manual reset. 

VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping integrity
of the system. Please follow the steps below prior to installation.

CAUTION

1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to warm-

up. This is particularly important during winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power inlet

connectors to a properly grounded and fused electrical supply, leaving electrical power to the unit turned off.

3. Turn the electrical power on. 

4. Verify that the evaporator blower or fan is running.

5. Observe the temperature on the digital display. The thermostat must be set a minimum of 10°F below this

temperature for the compressor to operate (the factory setting is 75°F). Refer to page 6 for instructions on
adjustment of the thermostat. 

6. The compressor in this air conditioner is protected by a phase sequence/phase loss detector. If the

compressor does not start when power is applied to the air conditioner, check to ensure all three phases
are energized. If voltage is present at all three phases, disconnect the power input and reverse two power
input leads. Reapply power and check for proper unit operation.

7. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering air
through their respective discharge ports. The cool air discharged should be less than 70°F when the room
temperature is between 70°F and 80°F. It is normal for the condenser blower to cycle on/off during this
period.  

8. Reset the thermostat to the factory setting of 75°F. 

WARNING: Operating the unit below 75°F may result

in freezing of the evaporator coil.

9. Turn off the electrical power and disconnect the air conditioner from the power source. 

10. If a cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity of the

closed-loop airflow system.

NOTE:

Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

The air conditioner must be standing in its proper mounting position for a minimum of five

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to

the compressor. To avoid compressor damage do not tip the unit more than 45° from its

proper mounting position.

Содержание Slimkool K3NA4C4SP28L

Страница 1: ...IS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 81 1 19 CDR 20131 SLIMKOOL SERIES K3...

Страница 2: ...c model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtual...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...H Cooling BTU H Max Ambient Temperature Min P S I G P S I G Design Pressure Low Side Design Pressure High Side Oz Factory Charge Refrigerant Max Fuse Size HACR Type Circuit Breaker Min Circuit Ampacit...

Страница 5: ...n discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperature...

Страница 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Страница 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Страница 8: ...trical power on 4 Verify that the evaporator blower or fan is running 5 Observe the temperature on the digital display The thermostat must be set a minimum of 10 F below this temperature for the compr...

Страница 9: ...m are for reference only and are subject to change WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 1 2 Mounting con t 1 These externally mounted air conditioners have pre installed gaskets...

Страница 10: ...3 TYP 27 94 709 6 66 16 8 4 00 101 6 TYP 13 54 343 9 TYP 11 79 299 4 2 75 70 0 TYP 3 96 100 5 1 11 28 1 3 07 78 0 2 64 67 0 10 37 263 3 1 59 40 3 8 76 222 5 DRAIN TUBE 5 83 148 0 1 48 37 5 1 2 2 3 4...

Страница 11: ...36 01 Transformer 0932 38 Fuses 2 0916 30 Phase Protector 0694 73 Overload 0694 72 Overload base 0694 74 Filter 9501F SLIMKOOL NEMA 4X model offered with these additional features Stainless Steel Shel...

Страница 12: ...or threshold setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and conden...

Страница 13: ...lity They are designed to require only routine maintenance If your air conditioner should require warranty service please contact Kooltronic If you require service out of warranty we have compiled a t...

Страница 14: ...difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Evaporator Coil...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: