Filter Removal and Service

Kooltronic Heat Exchanger feature an easily removable inlet filter to
facilitate necessary cleaning.

1)

Move the filter forward, using attached tab, to clear the
near filter retainer.  Pull the filter downward and toward you until the 
far side of the filter clears the far filter retainer.

2)

After removal, the filter should be flushed under warm running water 
with the clean side up, driving contaminants out the dirty side of the 
filter.  If the accumulated dirt is oily, washing in a detergent bath is 
recommended, followed by warm water rinse as above.

3)

The filter may be sprayed with 

Kooltronic A-16 Filter Recoating 

Adhesive

to trap fine airborne contaminants, or they can simply 

be dried and reinstalled as strainer type filters. 

Recoating

is recommended for the best results.

4)

Reinstall the filter:  (a) Holding the tab, slide the filter into the near 
retainer, (b) press filter against the unit and (c) slide forward into
far retainer.

CAUTION

Do not operate the Heat Exchanger for extended periods

of time with the filter removed.  The heat exchanger element

may become clogged with dust or lint from the ambient

environment.  A clogged heat exchanger element is not 

readily detected and will give the same reaction as clogged

filter.  A clean filter is the best protection.

VIII. Packing Procedure

Keep Heat Exchanger in proper upright position.

Pack Heat Exchanger in an appropriate carton (preferably original carton if possible),
with adequate internal protective packaging, making sure carton is marked properly.

For local controlled transportation, strap carton where possible, to a secure part of
truck to prevent falling or sliding, minimizing vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet.  Unpalletized ship-
ment risks severe damage which voids the warranty.

Содержание KTHE300

Страница 1: ... OPERATOR S MANUAL CAUTION BEFORE INSTALLING AND USING THIS HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 10 12 18 CDR 20111 ...

Страница 2: ...ic Heat Exchangers are designed for indoor applications with ambient temperatures from 50 F to 125 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general information for properly in...

Страница 3: ...you read and thoroughly under stand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification Label Each Kooltronic Heat Exchanger includes an identification label This label provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO MAX CABINET VOLTS FREQ ...

Страница 4: ...ed to any available vertical surface on the enclosure Refer to page 5 for location of all mounting holes and cutouts Make sure cutouts do not interfere with components inside your cabinet Proper alignment of air inlets and outlets is essential for optimum Heat Exchanger performance All Kooltronic externally mounted Heat Exchangers are fully gasketed to ensure proper sealing This seal is necessary ...

Страница 5: ...hes are for reference only and are subject to change KTHE300 MOUNTING PLAN Technical Data Max Approx Power Ambient Weight Model Amps Watts Temp F lbs KTHE300 3 0 275 125 60 KTHE500 3 0 275 125 70 60 Hz operation The technical data applicable to 230V units is same as for 115V except Amps are one half of 115V units Dimensions inches Performance Watts F Model A B C D E F G Air In Air Out KTHE300 281 ...

Страница 6: ...nd the nature of air borne particulate matter differs widely with each installation It is generally sufficient to remove and wash the reusable alu minum mesh air filter when the outer surface of these filters appear covered with a thin layer of dust or lint Filter recoating adhesive is recommended Appropriate dis posable filters are available from Kooltronic If filter service is neglected or delay...

Страница 7: ...ts 4 Reinstall the filter a Holding the tab slide the filter into the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected a...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: