VII. Specific Model Data
Mounting
The Kooltronic Special Purpose Air Conditioners K2A6C16NPT52L have been engineered to be installed
easily. Prior to mounting, refer to the mounting plan on page 8 showing dimensions and locations of
mounting holes and cutouts. Prior to cutting or drilling, make sure that cutouts and mounting holes do not
interfere with components inside the cabinet. To avoid damaging your air conditioner, please read the
following information before installation:
•
Install the two (2) mounting hooks using the four (4) supplied #10 screws, two screws for each
hook.
•
Refer to the mounting plan on page 8 for the location of all mounting holes and cutouts.
•
Make sure the cutouts don't interfere with components inside your cabinet.
•
Proper alignment of all air inlets and outlets is essential for optimum performance of the air
conditioner.
•
All externally-mounted air conditioners are fully gasketed to ensure proper sealing. This seal is
necessary to maintain the integrity of the closed loop system.
•
Hang air conditioner onto the enclosure.
•
Secure the air conditioner to the enclosure using the supplied hardware.
•
Use all existing mounting holes to insure stability and a tight seal.
•
Attach supplied drain hose to the drain exit on the lower side panel of the air conditioner.
•
The external drain hose must not be elevated above the exit port. Improper mounting will impede
the flow of condensate and may cause internal malfunctions.
CAUTION
If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will
support the additional weight of the air conditioner. Also be certain that when the door is
opened fully, the cabinet does not become unbalanced. The actual weight of the unit can be
found in the performance specifications.