V. Principles of Operation
Kooltronic Air Conditioners are required when the equipment
operating temperature must be kept near or lower than the
ambient room temperature, and/or the cabinet must be
sealed from dust, fumes, oil, corrosives and other
contaminants. These Air Conditioners utilize a "Closed-Loop
Cooling System" to ensure optimum performance of the
installed components.
Closed-Loop cooling seals the electronic enclosure from
hostile elements in the environment. Two separate
circulation systems are employed. The internal system cools
and dehumidifies the air inside the cabinet, totally isolating
the sensitive electronics and other components from the
environment. The external system uses circulating ambient
air or water to discharge the heat removed from the
electronics. The heat is dissipated from the enclosure by
means of the vapor compression refrigeration cycle. This
takes place in a hermetically-sealed refrigeration system,
utilizing either an air-cooled or water-cooled condenser heat
exchanger. The warm air inside the enclosure is drawn
through the evaporator coil where it is cooled, dehumidified
and returned.
Any enclosure moisture accumulated on the evaporator coil is collected in the condensate tray and
removed through the drain tube to the condensate evaporator. Condensate evaporates in the
condensate evaporator and is released to the ambient air by the condenser impeller.
The heat removed through the evaporator coil is transferred by the compressed refrigerant to the
condenser coil. Ambient air is then passed through the condenser coil, where it absorbs the heat and
is then discharged to the environment.
This unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing.
In conditions of low ambient temperature and low enclosure load, the thermostat regulates the
return air temperature from 75
o
F to 86
o
F. The standard set point of the Low Temperature Thermostat
is 75
o
F. The set point can be changed to 70
o
F or to 79
o
F by changing the location of the
thermostat jumper (See illustrations on page 8).
The Low Temperature Thermostat has a test start relay. When the air conditioner is turned on it will run
constantly for the first 15 minutes regardless of external temperatures. Afterwards, if the entering
evaporator air temperature is lower than the thermostat set point, the compressor and condenser
blower will stop, and the thermostat will begin to control the air conditioner.
The heater kit consists of a heater, a heat control thermostat and a heater limiter. The heater control
thermostat is a bimetal disk with a fixed set point of 60 F. When the entering evaporator air temperature
rises above 60
o
F the heater shuts off, and when the evaporator air temperature falls below 40
o
F the
heater will engage. The contact points of the alarm thermostat are normally closed. If the entering
evaporator air temperature exceeds 130
o
F the alarm thermostat contacts open, and when the
temperature drops below 130
o
F the contacts close.
A condenser blower thermostat is standard on this unit. The thermostat temperature sensor is installed
in the refrigerant liquid line. When the ambient temperature is above 95
o
F the condenser fan will run at
full speed. When the ambient temperature is lower than 95
o
F the condenser fan will cycle. In
applications having frequent voluntary heat load fluctuations, an optional Short Cycle Protector is
recommended.
When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75
o
F to
115
o
F enclosure temperature, depending on the ambient temperatures.
CO
N
DE
N
SER
AIR I
N
(2) PLACES
SUPPLY
AIR OUT
RETUR
N
AIR I
N
CO
N
DE
N
SER
AIR OUT
CO
N
DE
N
SER
AIR I
N
(2) PLACES
5
NPT52L
Содержание K2A6C16NPT52L
Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...