background image

V. Principles of Operation

Kooltronic Air Conditioners are required when the equipment
operating temperature must be kept near or lower than the
ambient room temperature, and/or the cabinet must be
sealed from dust, fumes, oil, corrosives and other
contaminants. These Air Conditioners utilize a "Closed-Loop
Cooling System" to ensure optimum performance of the
installed components.
Closed-Loop cooling seals the electronic enclosure from
hostile elements in the environment. Two separate
circulation systems are employed. The internal system cools
and dehumidifies the air inside the cabinet, totally isolating
the sensitive electronics and other components from the
environment. The external system uses circulating ambient
air or water to discharge the heat removed from the
electronics. The heat is dissipated from the enclosure by
means of the vapor compression refrigeration cycle. This
takes place in a hermetically-sealed refrigeration system,
utilizing either an air-cooled or water-cooled condenser heat
exchanger. The warm air inside the enclosure is drawn
through the evaporator coil where it is cooled, dehumidified
and returned.
Any enclosure moisture accumulated on the evaporator coil is collected in the condensate tray and
removed through the drain tube to the condensate evaporator. Condensate evaporates in the
condensate evaporator and is released to the ambient air by the condenser impeller. 
The heat removed through the evaporator coil is transferred by the compressed refrigerant to the
condenser coil. Ambient air is then passed through the condenser coil, where it absorbs the heat and
is then discharged to the environment.
This unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing.
In conditions of low ambient temperature and low enclosure load, the thermostat regulates the
return air temperature from 75

o

F to 86

o

F. The standard set point of the Low Temperature Thermostat

is 75

o

F. The set point can be changed to 70

o

F or to 79

o

F by changing the location of the

thermostat jumper (See illustrations on page 8).
The Low Temperature Thermostat has a test start relay. When the air conditioner is turned on it will run
constantly for the first 15 minutes regardless of external temperatures. Afterwards, if the entering
evaporator air temperature is lower than the thermostat set point, the compressor and condenser
blower will stop, and the thermostat will begin to control the air conditioner.
The heater kit consists of a heater, a heat control thermostat and a heater limiter. The heater control
thermostat is a bimetal disk with a fixed set point of 60 F. When the entering evaporator air temperature
rises above 60

o

F the heater shuts off, and when the evaporator air temperature falls below 40

o

F the

heater will engage. The contact points of the alarm thermostat are normally closed. If the entering
evaporator air temperature exceeds 130

o

F the alarm thermostat contacts open, and when the

temperature drops below 130

o

F the contacts close. 

A condenser blower thermostat is standard on this unit. The thermostat temperature sensor is installed
in the refrigerant liquid line. When the ambient temperature is above 95

o

F the condenser fan will run at

full speed. When the ambient temperature is lower than 95

o

F the condenser fan will cycle. In

applications having frequent voluntary heat load fluctuations, an optional Short Cycle Protector is
recommended. 
When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75

o

F to

115

o

F enclosure temperature, depending on the ambient temperatures.

CO

N

DE

N

SER

AIR I

N

(2) PLACES

 SUPPLY

 AIR OUT

 RETUR

N

 AIR I

N

CO

N

DE

N

SER

AIR OUT

CO

N

DE

N

SER

AIR I

N

(2) PLACES

5

NPT52L

Содержание K2A6C16NPT52L

Страница 1: ...NT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 034 12 1 19 CDR 20131 NPT SERI...

Страница 2: ...model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtuall...

Страница 3: ...5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper...

Страница 4: ...t type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTO...

Страница 5: ...ditions of low ambient temperature and low enclosure load the thermostat regulates the return air temperature from 75o F to 86o F The standard set point of the Low Temperature Thermostat is 75o F The...

Страница 6: ...is running 9 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers should be...

Страница 7: ...tlets is essential for optimum performance of the air conditioner All externally mounted air conditioners are fully gasketed to ensure proper sealing This seal is necessary to maintain the integrity o...

Страница 8: ...es mm are for reference only and are subject to change 2 06 52 3 17 4 3 2 60 66 0 2 1 1 2 4 3 J2 3 4 5 10 9 8 7 6 1 2 3 J1 CG RELAY CONTACTS N O 240 VAC 120 VAC TEMPERATURE SENSOR Mounting Holes 4 156...

Страница 9: ...MOUNTING HOOKS 45 11 4 TYP 2 94 74 6 1 36 34 5 15 25 387 3 1 00 25 4 31 7 8 52 71 1338 8 37 37 949 1 10 02 254 5 14 13 358 9 10 45 265 4 56 14 2 DRAIN 18 62 472 9 1 45 36 83 12 25 311 1 2 50 63 5 1 0...

Страница 10: ...52L Part Part Number Compressor 0665 404 Compressor Run Capacitor 0452 90 Condenser Blower Motor 0261 80 Condenser Motor Capacitor 0452 06 Evaporator Impeller 0194 108 Evaporator Impeller Capacitor 04...

Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and condenser coil service The rear panel must be removed in order to clean the filt...

Страница 13: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set p...

Страница 14: ...r Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Eva...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...