VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air Conditioners are designed to
require only the routine cleaning of air filters to assure unimpeded air flow through the condenser heat
exchanger. It is not possible to recommend specific filter cleaning intervals since the level and the nature of
airborne particulate matter differs widely with each installation. It is generally sufficient to remove and wash the
reusable aluminum mesh air filters when the outer surfaces of these filters appear covered with a thin layer of dust
or lint. Filter recoating adhesive is recommended. Appropriate disposable filters are available from Kooltronic.
If filter service is neglected or delayed, the air conditioner will not perform at its design capacity. The first
indication of excessively clogged air filters is usually a gradual increase of temperature within the equipment
cabinet. If operation is continued under these conditions, the compressor will be shut off by the thermal overload
device. The compressor will restart when its external temperature drops below the protector threshold setting and the
compressor will continue to cycle on and off. Continued operation under these conditions will cause damage,
shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning.

CAUTION

1) Lift the filter up by the bottom slot using a screw driver or similar tool. Pull filter toward you and downward

until the top of the filter clears the upper filter retainer.

2) After removal, the filters should be flushed under warm running water with the clean side up, driving

contaminants out the dirty side of the filter. If the accumulated dirt is oily, washing in a detergent bath is
recommended, followed by a warm water rinse as above.

3) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

to trap fine airborne

contaminants, or they may simply be dried and reinstalled as strainer type filters. 

Recoating is

recommended for best results.

4) Reinstall the filter: (a) keeping the slot at the bottom, slide filter into the upper retainer, (b) press filter

against the unit and (c) slide down into lower retainer.

CAUTION

B. Blowers

The design life of the blowers employed in all Kooltronic Air Conditioners is substantially in excess of
20,000 hours. All Kooltronic condenser and evaporator blowers are equipped with UL/CSA permanently-
lubricated precision ball-bearing motors, with automatic-reset thermal overload protectors.
If field replacement of a blower motor is necessary, most blower assemblies, including mounting plate, are
readily removable. Each of the blower mounting plates is held to the air conditioner cabinet structure by
screws and nuts. For installation of the replacement blower, electrical connections may be broken at the
terminal block, or power leads may be cut and appropriately spliced together. 

Before opening the air conditioner, disconnect all power.

Do not operate the air conditioner for extended periods of time with the filter removed. The

condenser coil may become clogged with dust or lint from the air entering the face. A

clogged condenser coil is not readily detected and will give the same reaction as a clogged

filter. A clean filter is the best protection.

Содержание K2A6C12HTL

Страница 1: ...S MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 66 1 19 CDR 20131 LARGE HORIZONTAL TO...

Страница 2: ...the specific model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...e that the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met...

Страница 5: ...mostat to prevent the evaporator coil from freezing In conditions of low ambient temperature and low enclosure load the thermostat regulates the return air temperature from 75 F to 86 F The standard s...

Страница 6: ...ning after three 3 to five 5 minutes 7 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and condenser...

Страница 7: ...lets and outlets is essential for optimum performance of the Air Conditioner Place supplied gasket on perimiter of enclosure cutouts All externally mounted Air Conditioners must be fully gasketed to e...

Страница 8: ...to change 2 06 52 3 17 4 3 2 60 66 0 2 1 1 2 4 3 J2 3 4 5 10 9 8 7 6 1 2 3 J1 CG RELAY CONTACTS N O 240 VAC 120 VAC TEMPERATURE SENSOR Mounting Holes 4 156 3 9 DIA ADJUSTING PINS 3 2 1 4 70 F Connect...

Страница 9: ...6 8 1 17 29 7 31 08 789 4 70 17 7 16 15 410 2 12 90 327 6 3 62 91 9 15 83 402 0 12 32 312 9 87 22 0 1 2 3 4 Drawings and Dimensions con t K2A6C12HTL Dimensions inches mm are for reference only and are...

Страница 10: ...12HTL Part Part Number Compressor 0665 401 Compressor Run Capacitor 0452 54 Condenser Motor 0261 80 Condenser Motor Capacitor 0452 06 Evaporator Impeller 0194 15 Evaporator Impeller Capacitor 0452 73...

Страница 11: ...the filter clears the upper filter retainer 2 After removal the filters should be flushed under warm running water with the clean side up driving contaminants out the dirty side of the filter If the...

Страница 12: ...onditioner from equipment controller or enclosure I Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under Section III PR...

Страница 13: ...or and Evaporator Blower Check Blower Capacitor are running Condenser Blower does Replace Condenser Blower not run Failed Condenser Blower Replace Condenser Blower Thermostat Thermostat or Sensor Repl...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: