12
C. Compressor
All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They are
hermetically sealed and charged at the factory, and equipped with automatic-reset thermal overload
protectors.
If the compressor or the hot gas bypass valve fails, it is strongly recommended that the air conditioner be
returned to Kooltronic for service.
D. Refrigerant Loss
Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and after
manufacture. It is possible that shipping or other damage, or microscopic leaks over a long period, may
result in the need for replenishment of refrigerant charge.
When it has been verified by a qualified
professional that a refrigerant shortage does exist, the leak must be repaired. Then the unit may be
evacuated and recharged in the field by qualified service people only.
CAUTION
E. Relocation
If your Kooltronic Air Conditioner has to be moved to another location by truck, the following precautions
should be taken:
I
De-mount Air Conditioner from equipment, controller or enclosure.
I
Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND
SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under
Section III.
"PRODUCT HANDLING".
Refer to the data on the unit nameplate which specifies the type of
refrigerant and the amount of charge in ounces.
.
IX. Trouble-Shooting
Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to
require only routine maintenance. If your air conditioner should require warranty service, please
contact Kooltronic. If you require service out of warranty, we have compiled a trouble-shooting chart
to assist your service personnel. If additional assistance is required contact Kooltronic at (609) 466-3400
.
Problem
Cause
Solution
Unit does not run.
No Power.
Check Power Source and electrical connection.
Check unit ON-OFF switch (UL Listed units only).
Check unit power cord connection to terminal block.
After initial 15 minute energization
Return temperature is
Normal Operation.
of air conditioner, compressor and
between Thermostat set
Check return air temperature.
condenser fan do not run.
point and differential
Check sensor connection on Thermostat.
(
75°F to 86°F).