background image

7

Output Alarm Connections

Located on the front panel of the air conditioner is an output alarm connection. Connection to the alarm is not
required for operation of the air conditioner. Each alarm output consists of a dry set of contacts which are to
be user connected to an external alarm system. The contacts are rated 1.0 amp at 30 VAC/DC. 

The alarms available are:

Power Failure - White wires in harness. A contact that closes when the supply voltage to the unit 
is interrupted.

Component Failure - Black and blue wires in the harness. A contact that opens when the compressor
experiences excessive high or low refrigerant pressures. 

24 Volt Output

A source of 24 VAC is available from the red and brown wires located in the output alarm harness.  

Harness wire color code:

VII. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to

warm-up. This is particularly important during winter months.

2. Refer to the identification label for proper electrical voltage and current requirements. Connect the

power cord to a properly grounded and fused electrical supply, leaving electrical power to the unit
turned off. Remove rear panel and two electrical box covers.

3

. Note the factory thermostat setting, which is 70°F.

4. Turn the electrical power on.

5. Verify that the evaporator blower is running. 

6. Send the cooling request input signal.

7. Verify that the damper is in closed (vertical) position and the compressor is running. The condenser

blower starts to run after 2 or 3 minutes.

The air conditioner must be standing in its proper mounting position for a minimum of five

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to

the compressor. To avoid compressor damage do not tip the unit more than 45° from its

proper mounting position.

Function

Wire Color

Power Failure

White and White

Component Failure

Black and Blue

24 VAC Output

Red and Brown

Содержание K2A3C30EP62-2

Страница 1: ...N BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 60...

Страница 2: ...14 XI Warranty 15 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and sha...

Страница 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Страница 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Страница 5: ...ill be off depending on ambient conditions The crankcase compressor heater allows the unit to start with an ambient temperature of 0 F This unit is also equipped with a Low Temperature Thermostat to p...

Страница 6: ...de The compressor and the condenser blower do not run The evaporator blower runs constantly drawing air from the outside through the air filter and the enclosure then discharging air to the outside th...

Страница 7: ...installation CAUTION 1 The unit must sit in an upright position at a minimum room temperature of 65 F to allow the system to warm up This is particularly important during winter months 2 Refer to the...

Страница 8: ...orator air temperature should be about 12 F higher than the ambient temperature 11 Turn off heating input signal and send input surge signal 12 Verify that the damper is in open horizontal position an...

Страница 9: ...d that the three additional supplied screws be used at approximately the middle of the unit height for proper gasket compression The screws must be started from inside your enclosure 5 Attach the supp...

Страница 10: ...14 740 2 29 11 739 3 26 27 667 2 12 75 323 9 93 23 6 AMBIENT AIR IN LEFT SIDE FRONT BOTTOM DRAIN LOCATION RIGHT SIDE BACK TOP PLENUM 24 17 613 9 18 20 462 3 ECONOMIZER AIR OUT 2 98 75 7 Drawings and D...

Страница 11: ...ponent Replacements K2A3C30EP62R Part Part Number Compressor 0665 57 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Ev...

Страница 12: ...LEGEND CR COMPRESSOR RELAY DA DAMPER ACTUATOR RELAY DT DAMPER THERMOSTAT HL HEATER LIMITER HR HEATER RELAY ICR INPUT COOLING REQUEST IHR INPUT HEAT REQUEST IPA INPUT PURGE ALARM ISA INPUT SMOKE ALARM...

Страница 13: ...ermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected...

Страница 14: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blo...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: