V. Principles of Operation

Kooltronic Air Conditioners are required when the equipment operating temperature must be kept near or lower than the ambient
room temperature, and/or the cabinet must be sealed from dust, fumes, oil, corrosives and other contaminants. These air
conditioners utilize a "Closed-Loop Cooling System" to ensure optimum performance of the installed components.

Closed-Loop cooling seals the electronic enclosure from hostile elements in the environment. Two separate circulation systems
are employed. The internal system cools and dehumidifies the air inside the cabinet, totally isolating the sensitive electronics and
other components from the environment. The external system uses circulating ambient air to discharge the heat removed from
the electronics. The heat is dissipated from the enclosure by means of the vapor compression refrigeration cycle. This takes place
in a hermetically-sealed refrigeration system, utilizing an air-cooled condenser heat exchanger. The warm air inside the enclosure
is drawn through the evaporator coil where it is cooled, dehumidified and returned.

The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil. Ambient air is
then passed through the condenser coil, where it absorbs the heat and is then discharged to the environment.

A condenser fan speed controller is standard on this unit. The condenser fan will run at full speed, or will be off, depending on
ambient conditions. The crankcase compressor heater allows the unit to start with an ambient temperature of 0°F. This unit is also
equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing. In conditions of low ambient
temperature and low enclosure load, the thermostat regulates the return air temperature from 75°F to 86°F. The standard set point
of the Low Temperature Thermostat is 75°F. The set point can be changed to 70°F or to 79°F by changing the location of the
thermostat jumper (see illustrations below).

The Low Temperature Thermostat has a test start relay. When the air conditioner is turned on it will run constantly for the first 15
minutes regardless of external temperatures. Afterwards, if the entering evaporator air temperature is lower than the thermostat
set point, the compressor and condenser blower will stop, and the thermostat will begin to control the air conditioner.

When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75°F to 115°F enclosure
temperature, depending on the ambient temperatures.

                     ENCLOSURE AIR
 OUT

                      CONDENSER AIR
 

 IN  (3 PLACES)

                     ENCLOSURE AIR
 IN

                      CONDENSER AIR
  

OUT

                      AIR IN

                      AIR OUT

EP62R

5

COOLING A/C MODE

ECONOMIZER MODE

 2.06

 [52.3]

 .17

 [4.3]

  

 2.60

 [66.0]

2

1

1

2

4

3

J2

3

4

5

10

9

8

7

6

1

2

3

J1

CG

RELAY
CONTACTS
N.O.

240 VAC

120 VAC

TEMPERATURE
SENSOR

Mounting Holes (4)
.156 [3.9] DIA.

ADJUSTING
PINS

3

2

1

4

70ºF - Connect 1 and 2

75ºF - Connect 1 and 3

79ºF - Connect 1 and 4

Thermostat Jumper

ELECTRONIC 

THERMOSTAT 

CONTROL

Electronic Thermostat Control

Dimensions, inches [mm], are for reference only 
and are subject to change.

Содержание K2A3C30EP62-2

Страница 1: ...N BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 60...

Страница 2: ...14 XI Warranty 15 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and sha...

Страница 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Страница 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Страница 5: ...ill be off depending on ambient conditions The crankcase compressor heater allows the unit to start with an ambient temperature of 0 F This unit is also equipped with a Low Temperature Thermostat to p...

Страница 6: ...de The compressor and the condenser blower do not run The evaporator blower runs constantly drawing air from the outside through the air filter and the enclosure then discharging air to the outside th...

Страница 7: ...installation CAUTION 1 The unit must sit in an upright position at a minimum room temperature of 65 F to allow the system to warm up This is particularly important during winter months 2 Refer to the...

Страница 8: ...orator air temperature should be about 12 F higher than the ambient temperature 11 Turn off heating input signal and send input surge signal 12 Verify that the damper is in open horizontal position an...

Страница 9: ...d that the three additional supplied screws be used at approximately the middle of the unit height for proper gasket compression The screws must be started from inside your enclosure 5 Attach the supp...

Страница 10: ...14 740 2 29 11 739 3 26 27 667 2 12 75 323 9 93 23 6 AMBIENT AIR IN LEFT SIDE FRONT BOTTOM DRAIN LOCATION RIGHT SIDE BACK TOP PLENUM 24 17 613 9 18 20 462 3 ECONOMIZER AIR OUT 2 98 75 7 Drawings and D...

Страница 11: ...ponent Replacements K2A3C30EP62R Part Part Number Compressor 0665 57 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Ev...

Страница 12: ...LEGEND CR COMPRESSOR RELAY DA DAMPER ACTUATOR RELAY DT DAMPER THERMOSTAT HL HEATER LIMITER HR HEATER RELAY ICR INPUT COOLING REQUEST IHR INPUT HEAT REQUEST IPA INPUT PURGE ALARM ISA INPUT SMOKE ALARM...

Страница 13: ...ermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected...

Страница 14: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blo...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...