X. Trouble-Shooting

Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to
require no routine maintenance other than the cleaning of ambient air filters. If your air conditioner
should require warranty service, please contact Kooltronic. If you require service out of warranty,
we have compiled a trouble-shooting chart to assist your service personnel. If additional assistance
is required contact Kooltronic at (609) 466-3400

.

Problem

Cause

Solution

Unit not Cooling

No Power

Check Power Source and
Electrical Connections

Loss of Refrigerant

Locate and repair leak

Evaporator or Condenser

Replace Motor, Capacitor or

Blower not operating

entire Assembly

Filter clogged

Clean or replace Filter

Clogged Evaporator or

Clean Coil

Condenser Coil

Low Temperature Control

Check sensor wire connections

sensor wires broken

Low Temperature Control

Replace Thermostat or Relay

(Thermostat) defective

when applicable

Failed Compressor

Replace Compressor

Ice on Evaporator Coil

Insufficient Heat Load or Unit

Contact Kooltronic

Oversized for Application

Failed Evaporator Blower

Replace Evaporator Blower
Motor or Assembly

Clogged Evaporator Coil

Clean Coil

Condensate draining

Enclosure not properly sealed

Check and seal all openings

continuously

Excessive opening of Enclosure

Eliminate the frequency of
door opening

Excessive vibration

Defective Motor in Blower

Replace Motor

Defective Wheel in Blower

Replace Wheel

Compressor Loose

Tighten Mounting Bolts

Compressor Inoperative

Low line Voltage

Check Nameplate Voltage
against supply

Loss of Compressor Oil

Replace Compressor

Loss of Refrigerant

Locate and repair leak

Failed Compressor Capacitor

Replace Capacitor

Thermal Overload

Contact Kooltronic

Power interruptions

Allow Compressor time to reset

Refrigerant or Oil leaks

Crack or pin hole in tubing or

Replace tubing or rebraze joint

brazed joint

Condensate on the outside Insufficient Heat Load or Unit

Contact Kooltronic

surface of the Enclosure

oversized for application

Содержание K2A3C30EP62-2

Страница 1: ...N BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 60...

Страница 2: ...14 XI Warranty 15 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and sha...

Страница 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Страница 4: ...that the power source matches these requirements r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRA...

Страница 5: ...ill be off depending on ambient conditions The crankcase compressor heater allows the unit to start with an ambient temperature of 0 F This unit is also equipped with a Low Temperature Thermostat to p...

Страница 6: ...de The compressor and the condenser blower do not run The evaporator blower runs constantly drawing air from the outside through the air filter and the enclosure then discharging air to the outside th...

Страница 7: ...installation CAUTION 1 The unit must sit in an upright position at a minimum room temperature of 65 F to allow the system to warm up This is particularly important during winter months 2 Refer to the...

Страница 8: ...orator air temperature should be about 12 F higher than the ambient temperature 11 Turn off heating input signal and send input surge signal 12 Verify that the damper is in open horizontal position an...

Страница 9: ...d that the three additional supplied screws be used at approximately the middle of the unit height for proper gasket compression The screws must be started from inside your enclosure 5 Attach the supp...

Страница 10: ...14 740 2 29 11 739 3 26 27 667 2 12 75 323 9 93 23 6 AMBIENT AIR IN LEFT SIDE FRONT BOTTOM DRAIN LOCATION RIGHT SIDE BACK TOP PLENUM 24 17 613 9 18 20 462 3 ECONOMIZER AIR OUT 2 98 75 7 Drawings and D...

Страница 11: ...ponent Replacements K2A3C30EP62R Part Part Number Compressor 0665 57 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Ev...

Страница 12: ...LEGEND CR COMPRESSOR RELAY DA DAMPER ACTUATOR RELAY DT DAMPER THERMOSTAT HL HEATER LIMITER HR HEATER RELAY ICR INPUT COOLING REQUEST IHR INPUT HEAT REQUEST IPA INPUT PURGE ALARM ISA INPUT SMOKE ALARM...

Страница 13: ...ermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are subjected...

Страница 14: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blo...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: