IX. Trouble-Shooting 

 

Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to 
require only routine maintenance. If your air conditioner should require warranty service, please 
contact Kooltronic. If you require service out of warranty, we have compiled a trouble-shooting chart 
to assist your service personnel. If additional assistance is required contact Kooltronic at (609) 466-3400

 

Problem

                                            Cause                                    Solution 

Unit does not run.

                                 No Power.                              Check Power Source and electrical connection.

                                                                                           Check unit ON-OFF switch (UL Listed units only).
                                                                                           Check unit power cord connection to terminal block.
                                                 

After initial 15 minute energization

       Return temperature is            Normal Operation. 

of air conditioner, compressor and

      between Thermostat set        Check return air temperature. 

condenser fan do not run.

                   point and differential              Check sensor connection on Thermostat. 

                                            (

75°F to 86°F). 

 

D. Refrigerant Loss

 

 

Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and after 
manufacture. It is possible that shipping or other damage, or microscopic leaks over a long period, may result 
in the need for replenishment of refrigerant charge.

 When it has been verified by a Certified EPA Technician 

that a refrigerant shortage does exist, the leak must be repaired. Then the unit may be evacuated and 
recharged in the field by a Certified EPA Technician only. 
 
 

CAUTION 

 
 
 
 

 

E.  Relocation

 

 

If your Kooltronic Air Conditioner has to be moved to another location by truck, the following precautions 
should be taken: 
 

De-mount the air conditioner from the equipment, controller or enclosure. 

Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF 
KOOLTRONIC AIR CONDITIONERS in this manual under 

Section III. "PRODUCT HANDLING".

Refer to the data on the unit nameplate which specifies the type of 

refrigerant and the amount of charge in ounces. 

C. Compressor

 

 

All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They are 
hermetically sealed and charged at the factory, and equipped with automatic-reset thermal overload 
protectors. 
 
If the compressor fails, it is strongly recommended that the air conditioner be returned to Kooltronic for 
service.

Содержание K A6C4NPT33L Series

Страница 1: ...ANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 034 13 12 21 CDR 20369 NPT SERIES K_A6C4NPT33L Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...c model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enclosures in capacities ranging from 1 000 to 30 000 BTU H Our closed loop design also ensures that your components will not be exposed to hot dirty operating c...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the nameplate for the corresponding voltage Do not exceed the maximum fuse size found on the name...

Страница 4: ...e or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRANTY UNAUTHORIZED SERVICE OR MODIFICATION COMPARTMENT ONLY NEMA EEMAC UL50 BY UNDERWRITERS LABORATORIES INC TYPE 1 SPECIAL PURPOSE AIR CONDITIONER EQUIPMENT TYPE 3R ...

Страница 5: ...or coil from freezing In conditions of low ambient temperature and low enclosure load the thermostat regulates the return air temperature from 75o F to 86o F The standard set point of the Low Temperature Thermostat is 75o F The set point can be changed to 70o F or to 79o F by changing the location of the thermostat jumper See illustration on page 8 The Low Temperature Thermostat has a test start r...

Страница 6: ...an is running 9 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers should be delivering air through their respective discharge ports The cool air discharged should be less than 70o F when the room temperature is between 70o F and 80o F 10 If ambient temperature is below 75...

Страница 7: ...tlets is essential for optimum performance of the air conditioner All externally mounted air conditioners are fully gasketed to ensure proper sealing This seal is necessary to maintain the integrity of the closed loop system Hang air conditioner onto the enclosure Secure the air conditioner to the enclosure using the supplied hardware Use all existing mounting holes to insure stability and a tight...

Страница 8: ...d are subject to change 2 06 52 3 17 4 3 2 60 66 0 2 1 1 2 4 3 J2 3 4 5 10 9 8 7 6 1 2 3 J1 CG RELAY CONTACTS N O 240 VAC 120 VAC TEMPERATURE SENSOR Mounting Holes 4 156 3 9 DIA ADJUSTING PINS 3 2 1 4 70ºF Connect 1 and 2 75ºF Connect 1 and 3 79ºF Connect 1 and 4 Thermostat Jumper ELECTRONIC THERMOSTAT CONTROL Electronic Thermostat Control Dimensions inches mm are for reference only and are subjec...

Страница 9: ...OWER CORD 9 58 243 3 32 83 833 8 7 07 179 5 TYP 2 57 65 2 TYP 57 14 4 1 97 50 0 TYP 44 11 1 12 27 311 6 7 24 183 8 5 93 150 6 11 60 294 6 33 8 3 FILTER P N 7131F DRAIN 3 3 4 2 2 1 K_A6C4NPT33L Dimensions inches mm are for reference only and are subject to change GA200533A Drawings and Dimensions FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ...

Страница 10: ...or Impeller 0194 92 0194 93 Evaporator Impeller Capacitor 0452 05 0452 73 Condenser Coil 0666 32 0666 32 Evaporator Coil 0666 32 0666 32 Filter 7131F 7131F Standard Features Built in Condensate Evaporator Condenser Impeller Controller Filter High Pressure Protector Low Temperature Control Thermostat Mounts Internally or Externally NEMA 12 3R Ratings Maintained UL50 UL CUL Listed Zero ODP Refrigera...

Страница 11: ...e protector threshold setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty CAUTION A Filter Removal and Service Remove the screw from the filter holder Remove the filter from the filter holder After removal flush filter under warm running water with the clean side up If accumulated di...

Страница 12: ...g and after manufacture It is possible that shipping or other damage or microscopic leaks over a long period may result in the need for replenishment of refrigerant charge When it has been verified by a Certified EPATechnician that a refrigerant shortage does exist the leak must be repaired Then the unit may be evacuated and recharged in the field by a Certified EPA Technician only CAUTION E Reloc...

Страница 13: ...Refrigerant leak Check for any obstruction of Evaporator airflow Check and seal all openings Excessive condensate Eliminate the frequency of door openings draining and loss of A C sensible cooling performance Unit overcooling Failed Thermostat Check Thermostat wire connections Evaporator Blower Condenser Replace Thermostat Blower and Compressor are running Failed Relay Replace Relay Compressor cyc...

Страница 14: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void war...

Отзывы: