VII. Specific Model Data

Mounting

Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your Air
Conditioner, please read the following information before installation:

1.

Loosen two screws on the bottom of the unit.

2.

See Figure 1 for proper M/TAB orientation.Place the M/TAB flush against the outside of the
enclosure to locate cutouts and mounting holes.

3.

Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (

1/

4

-20 screws/nuts/washers). NOTE: Make sure the screws are inserted with heads

on M/TAB side. Tighten nuts securely.

4.

Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by
sliding the slots located on the front panel on the hooks of the M/TAB. 

5.

Tighten two screws on the bottom of the unit and seal the unit against the enclosure. 

6.

Attach overflow drain hose supplied to the drain exit in bottom of the unit. 

CAUTION

If the Air Conditioner is mounted to the cabinet door you must be sure

that the door hinges will support the additional weight of the Air

Conditioner. Also be certain that when the door is opened fully, the

cabinet does not become unbalanced. The actual weight of the unit can

be found in the Technical Data on page 9.

7

Dimensions (inches) are for reference only and are subject to change.

MOUNTING PLAN

Warm Air Return
From Enclosure

Cool Air Supply
To Enclosure

Ambient Air In

Heated Ambient
Air Out

1.00

[25.4]

2.20

[55.9]

6.75

[171.5]

17.50

[444.5]

6.75

[171.5]

0.56

[14.2]

10.25

[260.4]

11.25

[285.8]

7.00

[177.8]

6.25

[158.8]

0.44

[11.2]

(6) .281 [7.1]

DIA. HOLES

9.31

[236.5]

0.50

[12.7]

1

2

FIGURE 1

RP17 SERIES

WARM AIR RETURN FROM
ENCLOSURE

COOL AIR OUTLET 
TO ENCLOSURE

1

2

Содержание Advantage K2A4C1RP17R

Страница 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 35 1 19 CDR 20131 ADVANT...

Страница 2: ...e of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all size...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Страница 5: ...by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator coil is tra...

Страница 6: ...layed start of 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the system...

Страница 7: ...n the hooks of the M TAB 5 Tighten two screws on the bottom of the unit and seal the unit against the enclosure 6 Attach overflow drain hose supplied to the drain exit in bottom of the unit CAUTION If...

Страница 8: ...4 277 9 9 54 242 3 7 60 193 0 1 56 39 6 12 35 313 7 1 00 25 4 DIA HOLE 6 18 157 0 2 21 56 1 1 3 4 2 Drawings and Dimensions RP17 SERIES 8 Dimensions inches are for reference only and are subject to ch...

Страница 9: ...ntrol Switch Low Temperature Control Thermostat NEMA 12 3R Ratings Maintained UL CUL Recognized Technical Data RP17 Series KA4C1RP17R 1000 125 0 115 100 60 50 7 0 7 5 64 K2A4C1RP17R 1000 125 0 230 200...

Страница 10: ...and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable...

Страница 11: ...ass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect re...

Страница 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...