VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will
verify the shipping integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum,

allowing the system to warm-up. This is particularly important in winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Then

connect the power cord to a properly grounded and fused electrical supply. Leave the
electrical power off.

3. Note the factory thermostat setting is 75°F.

4. Heat up sensor bulb in evaporator compartment to 98°F using heat pipe or light bulb.  

5. Turn electrical power on.

6. Verify that the evaporator blower or fan is running.

7. The compressor should start. On units equipped with a short cycle protector, the

compressor will have a delayed start of 6 minutes from the time power is applied to
the unit.  

8. Verify that the condenser blower or fan is running. Note, the start of the condenser fan

or blower will be delayed until the system pressures rise.

9. Operate the air conditioner for approximately ten (10) minutes. During this period no

unusual noise or vibration should be evident. Both the evaporator and condenser fans
or blowers should be delivering air through their respective discharge ports. The cool
air discharged should be less than 70°F when the room temperature is between 70
and 80°F.  

10. Turn off the electrical power source, and disconnect the air conditioner from the power

source.

11. If any cover plug is removed to adjust the unit, make certain to put back in place to

maintain the integrity of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a 
performance test.

The Air Conditioner must be standing in its proper mounting position for a

minimum of five (5) minutes prior to testing. Failure to follow this procedure

will cause permanent damage to the compressor.

6

Содержание Advantage K2A4C1RP17R

Страница 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 35 1 19 CDR 20131 ADVANT...

Страница 2: ...e of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all size...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Страница 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Страница 5: ...by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator coil is tra...

Страница 6: ...layed start of 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the system...

Страница 7: ...n the hooks of the M TAB 5 Tighten two screws on the bottom of the unit and seal the unit against the enclosure 6 Attach overflow drain hose supplied to the drain exit in bottom of the unit CAUTION If...

Страница 8: ...4 277 9 9 54 242 3 7 60 193 0 1 56 39 6 12 35 313 7 1 00 25 4 DIA HOLE 6 18 157 0 2 21 56 1 1 3 4 2 Drawings and Dimensions RP17 SERIES 8 Dimensions inches are for reference only and are subject to ch...

Страница 9: ...ntrol Switch Low Temperature Control Thermostat NEMA 12 3R Ratings Maintained UL CUL Recognized Technical Data RP17 Series KA4C1RP17R 1000 125 0 115 100 60 50 7 0 7 5 64 K2A4C1RP17R 1000 125 0 230 200...

Страница 10: ...and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable...

Страница 11: ...ass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect re...

Страница 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Страница 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: