V. Principles of Operation

Kooltronic Air Conditioners are required when the equipment operating temperature
must be kept near or lower than the ambient room temperature, and/or the cabinet
must be sealed from dust, fumes, oil, corrosives and other contaminants. These Air
Conditioners utilize a "Closed-Loop Cooling System" to ensure optimum performance
of the installed components.

Closed-Loop cooling seals the electronic enclosure from hostile elements in the
environment. Two separate circulation systems are employed. The internal system
cools and dehumidifies the air inside the cabinet, totally isolating the sensitive
electronics and other components from the environment. The external system
uses circulating ambient air or water to discharge the heat removed from the
electronics. The heat is dissipated from the enclosure by means of the vapor
compression refrigeration cycle. This takes place in a hermetically-sealed
refrigeration system, utilizing either an air-cooled or water-cooled condenser heat
exchanger. The warm air inside the enclosure is drawn through the evaporator coil
where it is cooled, dehumidified and returned.

Any enclosure moisture accumulated on the evaporator coil is collected in the condensate tray and removed through
the drain tube to the condensate evaporator. Condensate evaporates in the condensate evaporator and is released to
the ambient air by the condenser impeller. 

The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil. Ambient
air is then passed through the condenser coil, where it absorbs the heat and is then discharged to the environment.

When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75°F to 115°F enclosure
temperature, depending on the ambient temperatures.

CONTROL ACTION

The evaporator blower operates continuously. The compressor is cycled on and off by the action from the factory preset
programmable thermostat. A pressure switch controls the on/off action of the condenser blower.

The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the
set point: if the temperature increases and reaches set point plus differential the
compressor is started and then turned off when the temperature reaches the
set point value again.

In case of fault in the thermostat probe the start and stop of the compressor
are timed through preset parameters.

The programmable thermostat is located as shown in the upper right ISO
illustration. WARNING: the programmable device is preprogrammed and set
at the factory. In the event changes are needed the following instructions can
be used.

FRONT PANEL COMMANDS 

FRONT PANEL LED INDICATORS

- To display target set point; in programming mode it selects a parameter or confirms an operation.

(UP)

- To see the max. stored temperature; in programming mode it browses the parameter codes or increases the displayed value.

(DOWN)

- To see the min. stored temperature; in programming mode it browses the parameter codes or decreases the displayed value.

- To switch the instrument off, if onF = oFF.

- Not enabled.

(DEF)

- To start a manual defrost.

KEY COMBINATIONS

To lock and unlock the keyboard.

To return to the room temperature display.

To enter programming mode.

EVAPORATOR

AIR OUTLET

EVAPORATOR

AIR INLET

CONDENSER

AIR INLET

CONDENSER

AIR OUTLET

DSP23L

Содержание ACCESS Series

Страница 1: ...E READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 105 5 21 CDR 20322 Find additional information...

Страница 2: ...tronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit FILTER P N FUS...

Страница 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Страница 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Страница 7: ...enser blower to cycle on off during this period 8 Turn off the electrical power source and disconnect the air conditioner from the power source 9 If any cover plug is removed to adjust the unit make c...

Страница 8: ...URE PANEL 15 49 393 4 TYP 7 50 190 5 56 14 2 TYP 21 72 551 6 TYP 5 59 141 9 2 PLACES 135 TYP 4 03 102 3 1 25 31 7 1 69 42 9 0 11 45 290 8 7 38 187 4 1 51 38 3 6 21 157 7 49 12 4 TYP 7 99 202 9 TYP 11...

Страница 9: ...GURATION INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING REAR PANEL L BRACKETS 2 1 KA4C2DSP23L K2A4C2DSP23L KNA4C2DSP23L K2NA4C2DSP23L INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING FRONT...

Страница 10: ...OPTION R 11 2 8 38 9 5 26 6 6 1 37 34 7 R 19 4 7 11 80 299 7 20 75 527 1 7 48 190 0 1 03 26 2 70 17 8 CONDENSER AIR OUTLET 2 1 115 VOLT MODEL 230 VOLT MODEL DIGITAL THERMOSTAT EVAPORATOR AIR INLET NOT...

Страница 11: ...8 0718 40 0718 38 0718 40 Technical Data KA4C2DSP23L 2000 2373 122 20 115 60 5 03 15 K2A4C2DSP23L 2000 2360 122 20 230 60 2 87 15 K2A4C2DSP23L 2000 2170 122 20 230 50 2 3 15 KNA4C2DSP23L 2000 2373 122...

Страница 12: ...ff Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet...

Страница 13: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 14: ...mostat improperly set Low Temperature Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Uni...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: